Mestek TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS Installation Instructions And Parts Identification Download Page 8

8

INSTALLATION (continued) - GAS PIPING

 To avoid damage or possible personal injury, do not connect gas piping to this unit 

until a supply line pressure/leak test has been completed. Connecting the unit before completing the 
pressure/leak test may damage the unit gas valve and result in a fi re hazard.

 Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak 

tests. These valves may not be completely shut off, exposing the gas valve to excessive pressure and 
damage.

NOTICE: If more than one unit heater is to be served 
by the same piping arrangement, the total cu. ft./hr. 
input and length of pipe must be considered.

NOTICE: If the gas unit heater is to be fi red with LP 
gas, consult your local LP gas dealer for pipe size 
information.

NOTICE: HEATER INSTALLATION FOR USE WITH 
PROPANE (BOTTLED) GAS MUST BE MADE BY 
A QUALIFIED L.P. GAS DEALER OR INSTALLER.  
HE/SHE WILL INSURE THAT PROPER JOINT 
COMPOUNDS ARE USED FOR MAKING PIPE 
CONNECTIONS; THAT AIR IS PURGED FROM 
LINES; THAT A THOROUGH TEST IS MADE FOR 
LEAKS BEFORE OPERATING THE HEATER; AND 
THAT IT IS PROPERLY CONNECTED TO THE 
PROPANE GAS SUPPLY SYSTEM.

Before any connection is made to the existing line 
supplying other gas appliances, contact the local gas 
company to make sure that the existing line is of adequate 
size to handle the combined load.

1.  Determine the required Cu. Ft./Hr. by dividing the input  by 1000. For SI/Metric measurements: Convert BTU/Hr. to kilowatts. Multiply the units 
inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE GAS: 
Multiply the Cu. Ft./Hr. value by 0.633; then, use the table. 4. Refer to the metric conversion factors listed in the General Safety section for SI Unit 
measurement conversions.

 

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less, 

 

and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)

 

 

(Based on a 0.60 Specifi c Gravity Gas)

  Nominal  

 

 

Iron Internal 

Length of Pipe,  Feet (meters)  

 

  

Pipe Size

 

Diameter

 

10 20 30 40 50 60 70 80 90 100 

125 

150 

175 

200

 

Inch

 

Inch

  (3.0)  (6.1)  (9.1)  (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)

 

 

1/2 

0.622 

175 

120 97 82 73 66 61 57 53 50 44 40 37 35

   

 

(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)

 

 

3/4 0.824 360 250 200 170 151 138 125 118 110 103  93  84  77  72

   

 

(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)

 

1  1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135

   

 

(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)

 

1/4 

1.380 

1400 950 770 660 580 530 490 460 430 400 360 325 300 280

   

 

(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)

 

1/2 

1.610 

2100 

1460 

1180 990 900 810 750 690 650 620 550 500 460 430

   

 

(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)

 2  2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020  950  850  800
   

 

(112)  (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)

 

1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280

   

 

(178)  (123)  (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)

 3  3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280
   

 

(311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6)

 4  4.026 23000 

15800 

12800 

10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600

   

 

(651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)

Table 3 - Gas Pipe Size

PIPE SIZING
To provide adequate gas pressure to the gas unit heater, 
size the gas piping as follows:

1.  Find the cu. feet/hr. by using the following formula:
 

       

Cu. feet/hr. =

 Input BTU/Hr. 

 

 

 

                            

 1000

2.  Refer to Table 3. Match “Length of Pipe in Feet” 

with appropriate “Gas Input - Cu. Feet/Hr.” figure. 
This fi gure can then be matched to the pipe size at 
the top of the column.

 Example:
 

It is determined that a 67 foot (20.4m) run of gas 
pipe is required to connect a 200 MBTU gas unit 
heater to a 1,000 BTU/cu feet (0.29kW) natural gas 
supply.

 

  

200,000 BTU/Hr      

= 200 Cu. feet/hr.

  1,000 

BTU/cu. 

feet 

 

Using Table 3, a 1 inch pipe is needed.

NOTE: See General Safety Information section for 
English/Metric unit conversion factors.

Summary of Contents for TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS

Page 1: ...t any problem that may be found RECEIVING INSTRUCTIONS Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment After the unit has been uncrated c...

Page 2: ...on Air 5 7 Proper Clearances 5 7 Suspension of Units 5 7 Heat Throw Data 6 Gas Piping 8 9 ELECTRICAL CONNECTIONS 10 11 12 VENTING 13 14 15 16 17 OPERATION Explanation of Controls and Operation 18 Main...

Page 3: ...t Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice versa will create risk of gas lea...

Page 4: ...9 279 311 311 311 E Hanging Distance Width 18 5 8 18 5 8 18 5 8 30 5 8 30 5 8 30 5 8 48 5 8 48 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 3...

Page 5: ...ve the floor must be equipped with an OSHA approved fan guard Refer to the latest edition of NFPA 88A Parking structures In Canada installation must be in accordance to the latest edition of CSA B149...

Page 6: ...NR NR 44 47 58 66 71 75 6 1 13 4 14 3 17 7 20 1 21 6 22 9 60 8 75 80 85 90 95 110 125 130 138 2 4 22 9 24 4 25 9 27 4 29 0 33 5 38 1 39 6 42 1 10 65 70 75 79 83 95 109 115 120 3 0 19 8 21 3 22 9 24 1...

Page 7: ...ere is a possibility of distortion or discoloration of adjacent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of t...

Page 8: ...vity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Diameter 10 20 30 40 50 60 70 80 90 100 125 150 175 200 Inch Inch 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0...

Page 9: ...al Fuel Gas Code in Canada according to CSA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating valve in the line ups...

Page 10: ...tical vibration free surface free from air currents and in accordance with the furnished instructions Mount the thermostat approximately 5 feet 1 5m above the floor in an area where it will be exposed...

Page 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5d Tubular Units Equipped with Natural Gas and Propane LP Gas...

Page 12: ...12 ELECTRICAL CONNECTIONS continued Figure 5e Tubular Unit Sizes with Optional 2 Stage Ignition...

Page 13: ...operating the gas unit heater will result in the spillage of flue gas into the occupied space 9 Avoid installing units in areas under negative pressure due to large exhaust fans or air conditioning W...

Page 14: ...isance or hazard or could be detrimental to the operation of regulators relief valves or other equipment The vent pipe equivalent length must not exceed 50 feet 15 2m Equivalent length is the total le...

Page 15: ...r in the absence of local codes with current CSA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CSA B149 2 Installation Codes for Propane Gas Burning Appliances and Equi...

Page 16: ...16 Figure 8A Figure 8B VENTING continued D3620F D3619C...

Page 17: ...17 VENTING continued Figure 9A Figure 9B D3661F D3662D...

Page 18: ...motor is de energized 6 The fan operation is delayed 30 seconds once the thermostat is closed and continues operation for 30 seconds after the thermostat opens NOTICE The start up fan delay must not e...

Page 19: ...eaters must be field derated to 90 of the normal altitude rating and be so marked in accordance with ETL certification See Table 6A for field deration information Check the gas input rate as follows R...

Page 20: ...Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting the manifold pressure Manifold Pressure Inc WC PROPANE LP GAS NATURAL GAS Heating Value BTU Hr Altitude Feet 8 6...

Page 21: ...t openings 3 Clean heat exchanger Refer to Installation 4 Determine cause and repair accordingly 1 Inspect all gas piping and repair 2 Check to ensure gas test ports are seated 3 Clean heat exchanger...

Page 22: ...tat 1 Replace or tighten 2 Clean power ventor wheel 3 Realign power ventor wheel 1 Check and tighten wires on fan circuit 2 Test for 115v on terminal ACB Heat and L2 if voltage is present replace moto...

Page 23: ...heat If not present and all checks are normal replace 1 Check power ventor circuit per wiring diagram 2 Check motor voltage and amp draw to motor name plate replace if motor found defective 3 Check f...

Page 24: ...er 3 5 Amp fuse on circuit board 1 Common side of transformer grounded to chassis 2 Loose spark ignitor 1 Gas supply off or gas supply pressure too low 2 Flame sense rod contaminated or loose wire 3 G...

Page 25: ...supplied with your unit NOTICE The heater and vent system should be checked once a year by a qualified technician All Maintenance Service information should be recorded accordingly on the Inspection...

Page 26: ...ing halogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 This limited warranty is conditional upon a advising the installing contractor who in turn n...

Page 27: ...ICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Hard...

Page 28: ...Venter Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s cu...

Page 29: ...29 NOTES...

Page 30: ...30 NOTES...

Page 31: ...11 Supply Voltage SV 1 115 1 60 5 230 3 60 2 208 1 60 6 460 3 60 3 230 1 60 7 575 3 60 4 208 3 60 Z Other Note Supply Voltage SV 2 7 include field mounted step down transformer 12 Motor Type MT 1 Ope...

Page 32: ...s equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Ch...

Reviews: