![Mestek TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS Installation Instructions And Parts Identification Download Page 4](http://html1.mh-extra.com/html/mestek/tubular-gas-fired-direct-spark-propeller-unit-heaters/tubular-gas-fired-direct-spark-propeller-unit-heaters_installation-instructions-and-parts-identification_1775689004.webp)
4
Table 1 - Performance and Dimensional Data - Tubular Propeller Unit Heater
DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 2 - Dimensional Drawing – Tubular Propeller Unit Heater
D4617C
Unit Size
100 125 150 175 200 250 300 350 400
PERFORMANCE DATA†
Input
-
BTU/Hr.
100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
(kW)
(29.3) (36.6) (43.9) (51.2) (58.6) (73.2) (87.8) (102.5)
(117.1)
Output
-
BTU/Hr.
83,000 103,750 124,500 145,250 166,000 207,500 249,000 290,500 332,000
(kW)
(24.3) (30.4) (36.4) (42.5) (48.6) (60.7) (72.9) (85.1) (97.2)
Thermal Effi
ciency
(%)
83 83 83 83 83 83 83 83 83
Free Air Delivery - CFM
1,600
2,200
2,400
2,850
3,200
3,450
5,000
5,600
5,800
(cu.
m/s)
(0.756) (1.039) (1.133) (1.346) (1.511) (1.629) (2.361) (2.644) (2.738)
Air
Temperature
Rise
-
°F
47 42 47 46 47 54 45 47 51
(°C)
(26)
(23)
(26)
(26)
(26)
(30)
(24)
(26)
(28)
Full
Load
Amps
at
120V
6.4 6.9 6.9 8.0 8.0 8.0 11.3
13.5
13.5
MOTOR DATA: Motor HP (Qty)
1/10
1/4
1/4
1/3
1/3
1/3
1/4 (2)
1/3 (2)
1/3 (2)
Motor
kW
(0.080) (0.19) (0.19) (0.25) (0.25) (0.25) (0.19) (0.25) (0.25)
Motor
Type
SP PSC PSC PSC PSC PSC PSC PSC PSC
RPM
1,050
1,140
1,140
1,140
1,140
1,140
1,140
1,140
1,140
Amps
@
115V 4.2 4.7 4.7 5.8 5.8 5.8 9.4 11.6
11.6
DIMENSIONAL DATA - inches (mm)
"A" Overall Height to Top of Flue
33-3/4
33-3/4
33-3/4
33-3/4
33-3/4
33-3/4
34
34
34
(857) (857) (857) (857) (857) (857) (864) (864) (864)
"B"
Jacket
Width
of
Unit
20-3/4 20-3/4 20-3/4 32-3/4 32-3/4 32-3/4 50-3/4 50-3/4 50-3/4
(527) (527) (527) (831) (831) (831) (1289)
(1289)
(1289)
"C"
Width
to
CL
Flue
13-3/8 13-3/8 13-3/8 19-3/8 19-3/8 19-3/8 28-3/8 28-3/8 28-3/8
(340) (340) (340) (492) (492) (492) (721) (721) (721)
"D" Depth to Rear of Housing
11
11
11
11
11
11
12-1/4
12-1/4
12-1/4
(279) (279) (279) (279) (279) (279) (311) (311) (311)
"E"
Hanging
Distance
Width
18-5/8 18-5/8 18-5/8 30-5/8 30-5/8 30-5/8 48-5/8 48-5/8 48-5/8
(473) (473) (473) (778) (778) (778) (1235)
(1235)
(1235)
"F"
Discharge
Opening
Width
18-3/4 18-3/4 18-3/4 30-3/4 30-3/4 30-3/4 48-3/4 48-3/4 48-3/4
(476) (476) (476) (781) (781) (781) (1238)
(1238)
(1238)
"G"
Depth
to
CL
Flue
4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 5-1/8 5-1/8 5-1/8
(121) (121) (121) (121) (121) (121) (130) (130) (130)
"L"
Overall
Unit
Width
25-1/4 25-1/4 25-1/4 37-1/4 37-1/4 37-1/4 55-1/4 55-1/4 55-1/4
(641) (641) (641) (946) (946) (946) (1403)
(1403)
(1403)
"M"
Flue
Size
Diameter*
-
in 5 5 5 5 5 5 6 6 6
(mm)
(127)
(127)
(127)
(127)
(127)
(127)
(152)
(152)
(152)
Fan Diameter - in (Qty)
16
16
16
18
18
18
16 (2)
18 (2)
18 (2)
Gas
Inlet,
Natural
Gas
-
in
1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4
Gas Inlet, LP Gas - in
1/2
1/2
1/2
1/2
1/2
1/2 OR 3/4
1/2 OR 3/4
1/2 OR 3/4
1/2 OR 3/4
Approximate
Unit
Weight
-
lb
133 145 155 191 201 211 307 321 335
(kg)
(60)
(66)
(70)
(87)
(91)
(96)
(139)
(145)
(152)
Approximate
Ship
Weight
-
lb 173 185 195 241 251 261 367 381 395
(kg)
(78)
(84)
(88)
(109)
(114)
(118)
(166)
(173)
(179)
† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be fi eld derated 4% for each
1,000 ft. (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be fi eld derated
to 90% of the normal altitude rating, and be so marked in accordance with the ETL certifi cation. See Table 6A for fi eld deration information.
* Flue collar is factory supplied with unit; to be fi eld installed per included instructions. LEGEND: SP= Shaded Pole, PSC= Permanent Split Capacitor
Summary of Contents for TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS
Page 16: ...16 Figure 8A Figure 8B VENTING continued D3620F D3619C...
Page 17: ...17 VENTING continued Figure 9A Figure 9B D3661F D3662D...
Page 29: ...29 NOTES...
Page 30: ...30 NOTES...