4.
Unit Configuration:
On board DIP switches of DIPB are used for the below configurations.
SW1
PR-O contact setting
0
Economy contact
1
Window contact
SW2
System setting
0
2-pipes system
1
4-pipes system
SW4
Preheat setting
1
82.4°F
0
96.8°F
5.
Motorized Fan Speed Settings for Different Models on DIPB:
Unit Model
Speed (RPM)
SW3
SW5
SW6
Low
Medium
High
HW-04
500
600
700
0
0
0
HW-06
600
700
900
0
1
0
HW-12
600
700
950
0
0
1
HW-15
700
800
1100
0
1
1
HW-18
900
1100
1300
1
0
0
HW-20
800
900
1100
1
0
1
HW-24
900
1100
1200
1
1
0
HW-30
900
1200
1350
1
1
1
Default RPM
900
1200
1350
1
1
1
6.
Mode configuration:
DIPA-S1
Model
SW7
SW8
Model setting
0
0
Cool-Heat
0
1
Cool-Heat + booster heater
1
0
Cooling only
1
1
Cool + primary heater
7.
Air Conditioner ON/OFF
There are 3 ways to turn the system on or off:
a)
By the ON/OFF button on the handset or wired wall pad.
b)
By the programmable timer on the handset or wired wall pad.
c)
By the manual control button on the air conditioner.
8.
Power On Setting
a)
Handset only user interface: When the power ON signal is received by the air conditioner, the Mode, Fan
Speed, Setting temperature and Swing setting will be the same as the handset setting before the last power
OFF.
b)
Wall-pad only OR wall-pad and handset user interface: When the power ON signal is received by the air
conditioner, the Mode, Fan Speed, Setting temperature, Swing setting and Timer ON/OFF weekly
program will be the same as the wall pad setting before the last power OFF.