Using Remote Control Handset to Set Master Control Unit:
a)
Connect all the units PCBs according to the wire color and type of connector.
b)
Select the master unit by setting DIPA‐S1 SW6 to ON (=1) in the PCB.
c)
Ensure the DIPA‐S1 SW6 is set to OFF (=0) in the PCB on each slave unit.
d)
Switch on the units by connecting the main power supply.
e)
Using the handset, set the operation parameters for the master unit which will automatically send the settings to
the slave unit.
f)
Master unit will beep twice confirming receipt of commands while the slave unit will beep once.
Using Wall pad to Set Master Control Unit:
a)
Connect all the units’ PCBs according to the wire color and type of connector.
b)
Select the master unit by setting DIPA‐S1 SW6 to ON (=1) in the PCB.
c)
Ensure the DIPA‐S1 SW6 is set to OFF (=0) in the PCB on each slave unit.
d)
Provide each slave unit with an addressable code by configuring SW1 – SW5 of DIPA‐S1 according to the DIP
switch setting table.
e)
Switch on the units by connecting the main power supply.
f)
Using the wall pad set the operation parameters for the master unit which will send the setting to the slave units
by Global‐control communication or Addressable communication methods.
g)
Master unit will beep twice confirming receipt of commands while the slave unit will beep once.
MASTER-SLAVE CONTROL
The control PCB can receive data from both wireless LCD handset and wired wall pad.