Form 43343350
Dec 2017
-47-
B.
INDIRECT VENTING (UNVENTED HEATERS) — This heater requires ventilation in the building to dilute the
products of combustion and provide fresh air for efficient combustion. Where unvented heaters are used,
gravity or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input
of installed heaters. Exhaust vents must be located at the highest point above and in the vicinity of the
heaters, and the inlet vents must be located below the level of the heaters. An exhaust hood (Part
#42924000) must be placed on the flue adapter collar located on the end of the last body section when
used unvented and must be mounted only in a downward position as shown.
17.0)
AIR FOR COMBUSTION
If indoor combustion air is to be supplied for a tightly enclosed area, one square inch of free area opening shall
be provided below the heater for each 1,000 Btu/hr of heater input. When outside air is used, the opening below
the heater shall be one square inch of free area for each 4,000 Btu/hr of heater input. In contaminated
atmospheres or high humidity areas, optional outside air for combustion is recommended. Adequate clearances
around the air inlet screen must be maintained at all times. In larger open areas of buildings, infiltration
normally is adequate to provide air for combustion.
17.1)
DIRECT OUTSIDE AIR FOR COMBUSTION
Outside combustion air should be supplied directly to the heater when the building is subject to negative
pressure, or when contaminants or high humidity are present in the building air. These contaminants include
paints, solvents, corrosive vapors or any other foreign particles that may cause damage to the heater or result in
poor combustion.
Outside combustion air can be brought directly to the heater by a 4” diameter duct less than 50 ft. long or
equivalent (see table in Section 16.0) based on selected model and heat exchanger lengths). This is attached to
the 4” diameter starting collar (supplied with heater). The starting collar is fitted to the rear of the burner box
cabinet as shown below. An approved vent cap must be placed directly on the end of the outside combustion air
inlet pipe. The combustion air inlet should be not less than 3 ft. (0.9m), either vertically or horizontally, from the
flue vent termination. The air intake terminal must be located not less than 1 ft. (30cm) above grade. It is good
installation practice to supply combustion air from the same pressure zone as the vent outlet. Avoid bringing
combustion air to the heater from an attic space. There is no guarantee that adequate combustion air will be
supplied.
If the heater is installed less than 2 ft. from the ceiling, a combustion air inlet kit PN 44129510 must be
provided to allow for expansion/contraction of straight series tube heaters.
In colder climates, where necessary, insulate the outside combustion air duct.
Summary of Contents for 44488010
Page 15: ...Form 43343350 14 Dec 2017 7 1 TYPICAL ASSEMBLY LAYOUT STRAIGHT SERIES SHOWN ...
Page 16: ...Form 43343350 Dec 2017 15 8 0 DIMENSIONS STRAIGHT SERIES Typical Dimensions Up to 60 Ft Shown ...
Page 17: ...Form 43343350 16 Dec 2017 8 1 DIMENSIONS U SERIES Typical Dimensions Up to 50 Ft Shown ...
Page 18: ...Form 43343350 Dec 2017 17 8 2 HEATER ASSEMBLY JOINING OF TUBE SECTIONS ...
Page 19: ...Form 43343350 18 Dec 2017 ...
Page 52: ...Form 43343350 Dec 2017 51 20 0 CONTROL COMPONENT LOCATION ...
Page 54: ...Form 43343350 Dec 2017 53 22 0 TROUBLESHOOTING GUIDE SINGLE STAGE N1 L1 ...
Page 55: ...Form 43343350 54 Dec 2017 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED ...
Page 56: ...Form 43343350 Dec 2017 55 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED ...
Page 57: ...Form 43343350 56 Dec 2017 22 1 TROUBLESHOOTING GUIDE TWO STAGE N2 L2 ...
Page 58: ...Form 43343350 Dec 2017 57 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED ...
Page 59: ...Form 43343350 58 Dec 2017 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED ...
Page 66: ...Form 43343350 Dec 2017 65 ...