29
BA 2076/02/01
< Input/output configuration > tab
< Input/output configuration > tab
< Input/output configuration > tab
< Input/output configuration > tab
< Input/output configuration > tab
•
Ambient temperature:
Ambient temperature:
Ambient temperature:
Ambient temperature:
Ambient temperature: This function activates a recording of the ambient temperature. For further details, please refer to page
10 of chapter 4.2 (Electrical connection - Sensor inputs) as well as page 13 of chapter 5.2 (Function Description - Sensor
inputs).
•
Oil temperature input:
Oil temperature input:
Oil temperature input:
Oil temperature input:
Oil temperature input: This field can be used to parameterize your input sensor (Pt100 or 4…20mA). For more information, see
page 10 in chapter 4.2 (Electrical Connection of the Sensor Inputs) and page 13 in chapter 5.2 (Function Description of the
Sensor Inputs).
•
Oil temperature and winding temperature output:
Oil temperature and winding temperature output:
Oil temperature and winding temperature output:
Oil temperature and winding temperature output:
Oil temperature and winding temperature output: This field can be used to parameterize the two analog outputs separately
from each other to the following output signals:
0 to 20 mA (error signal > 22 mA)
4 to 20 mA (error signal > 22 mA)
4 to 20 mA (error signal < 3.6 mA)
0 to 1 mA
0 to 10 V
For more information on the output signals, see page 11 in chapter 4.4 (Electrical Connection of the Analog Outputs) and
page 13 in chapter 5.3 (Function Description of the Analog Outputs).
•
Winding configuration:
Winding configuration:
Winding configuration:
Winding configuration:
Winding configuration: This function can be used to mask out the simulation of the winding temperature when you only
want to use the device for cooling system control via the oil temperature, for instance. When the simulation of the winding
temperature is masked out <Winding off>, all fields and menus which pertain to the winding temperature also disappear.
These include, among others, the life consumption calculation, the winding parameterization and the analog output for the
winding temperature.
8
Visualization Software
Summary of Contents for MTeC EPT202