Indication and Parameterization
Act.Load-Current
426 A
_
Load-Factor (K)
56,29
_____
TTTTTemper
emper
emper
emper
emperatur
atur
atur
atur
ature corr
e corr
e corr
e corr
e correction
ection
ection
ection
ection
This function can be used to correct
temperature losses on the thermometer
pocket.
The default setting is „temperature correction“ off
<Temp-Cor.OFF>.
When <Temp-Cor.ON> is activated, a correction value is set
internally which was determined from studies of temperature
measuring devices and sensors on transformers. The
temperature loss due to the thermometer pocket begins at an
oil temperature of approx. 30 °C and increases as the oil
temperature rises.
Actual load curr
Actual load curr
Actual load curr
Actual load curr
Actual load current
ent
ent
ent
ent
This menu item can be used to indicate
the actual load current. This results from
the actually fed in CT current multiplied
by the CT current ratio.
Curr
Curr
Curr
Curr
Current load factor
ent load factor
ent load factor
ent load factor
ent load factor
The load factor K specifies the ratio
between load current and rated current.
If the rated current is 1000 A and the
actual load current is 500 A, the load
factor is 0.5 (the load of the transformer
is 50%).
7.7
7.7
7.7
7.7
7.7
<DA
<DA
<DA
<DA
<DATTTTTA-LOGGING> Menu
A-LOGGING> Menu
A-LOGGING> Menu
A-LOGGING> Menu
A-LOGGING> Menu
This menu can be used to parameterize
the default settings for the data logging
function. This function can only be
performed with visualization software
which is available as an option.
For more information on this function, see page 15 in
chapter 5.10.
<Date/Time> Menu item
<Date/Time> Menu item
<Date/Time> Menu item
<Date/Time> Menu item
<Date/Time> Menu item
This submenu can be used to set the
current time and date. This menu also
appears when the device is powered up
for the first time or after a longer period
of time.
<-DATA-LOGGING->
Date/Time
_
DataLog-Counts
DataLog-Interval
-DATE-
[dd.mm.yyyy]
05.
11
.2004
Save ?
YES
NO
_
DataLog-Counts
12684
___
<DataLog-Counts> and
<DataLog-Counts> and
<DataLog-Counts> and
<DataLog-Counts> and
<DataLog-Counts> and
<DataLog-Interval> Menu Items
<DataLog-Interval> Menu Items
<DataLog-Interval> Menu Items
<DataLog-Interval> Menu Items
<DataLog-Interval> Menu Items
The <DataLog-Counts> menu item is
used to indicate the number of data
records which are currently stored.
The <DataLog-Interval> menu item can
be used to set the data logging interval
when the key lock has been released. The
default setting is 10 minutes.
7.8
7.8
7.8
7.8
7.8
<LIFE-CONSUM.> Menu
<LIFE-CONSUM.> Menu
<LIFE-CONSUM.> Menu
<LIFE-CONSUM.> Menu
<LIFE-CONSUM.> Menu
This menu can be used to parameterize
the life consumption calculation and
indicate the hotspot temperature and the
life consumption.
For more information on the life
consumption calculation, see page 14 in chapter 5.9.
Configuring the life consumption calculation
Configuring the life consumption calculation
Configuring the life consumption calculation
Configuring the life consumption calculation
Configuring the life consumption calculation
This menu item can be used to configure
the calculation algorithm (calculation as
per ANSI or IEC standard) or to mask out
the calculation.
Calculation as per ANSI standar
Calculation as per ANSI standar
Calculation as per ANSI standar
Calculation as per ANSI standar
Calculation as per ANSI standard C57.9
d C57.9
d C57.9
d C57.9
d C57.91-1995 (+err
1-1995 (+err
1-1995 (+err
1-1995 (+err
1-1995 (+errata)
ata)
ata)
ata)
ata)
Recommended for transformers whose construction is
dominated by the US American standards ANSI or IEEE.
Calculation as per IEC 354, second edition 199
Calculation as per IEC 354, second edition 199
Calculation as per IEC 354, second edition 199
Calculation as per IEC 354, second edition 199
Calculation as per IEC 354, second edition 1991-9
1-9
1-9
1-9
1-9
Recommended for transformers whose construction was
based on IEC standards.
Masking out the calculation (OFF)
Masking out the calculation (OFF)
Masking out the calculation (OFF)
Masking out the calculation (OFF)
Masking out the calculation (OFF)
When the device is installed on a transformer as a retrofit
and the expected lifespan is unknown, the calculation
algorithm can be masked out.
Expected lifespan
Expected lifespan
Expected lifespan
Expected lifespan
Expected lifespan
This menu item can be used to
parameterize the expected lifespan for
the insulation system of the transformer.
Config Life-Con.
Calculate ANSI
Calculate IEC354
Off
Save ?
YES
NO
_
Temp-Correction
_
Temp-Cor. ON
__
Temp-Cor. OFF
_
Save ?
YES
NO
DataLog-Interval
15
min
Save ?
YES
NO
_
normal Life
_
30
Year
Save ?
YES
NO
_
<-LIFE-CONSUM.->
Config Live-Con.
normal Life
_
Life-Consumption
NOTE
NOTE
NOTE
NOTE
NOTE
Please take into consideration that this device does not
automatically switch between summer and winter time and
subsequently, time differences can occur.