Setting ranges
Setting ranges
Setting ranges
Setting ranges
Setting ranges
Parameter
Parameter
Parameter
Parameter
Parameter
Remarks
Remarks
Remarks
Remarks
Remarks
Step Size
Step Size
Step Size
Step Size
Step Size
Temperature range, analog output 1
Calibration at plant: -20 to +140 °C
1 °C
(specifies the range of sensor input
(others on request)
and analog output 1)
Temperature range analog output 2
Calibration at plant: 0 to +160 °C
1 °C
(others on request)
Data logging interval
5 to 1440 min.
1 min.
Test function
0 to 150% of temperatur range
0.1 °C
(standard -20 to +220 °C)
Zero point correction
± 10 % of temperature range
0.1 K
(standard -16.0 to 16.0 K)
RS 485 address
0 to 79
Load change interval
0 to 9999 h
1 h
Switching points S1 to S4
Adjustable between
0.1 °C
hysteresis and 150% of
temperature range
Hystereses S1 to S4
Min. of 1% of temperature range
0.1 K
Delay times S1 to S4
0 to 120 sec.
0.1 sec.
Switching points ALARM, TRIP
Adjustable between
0.1 °C
hysteresis and 150% of
temperature range
Hystereses ALARM, TRIP
Min. of 1% of temperature range
0.1 K
Delay times ALARM, TRIP
0 to 120 sec.
0.1 sec.
CT transformer ratio
1 to 5000:1
1
Hotspot factor (H)
1.0 to 2.0
0.1
CT rated current
0.50 to 5.00 A
0.01A
Gradient (gr)
0.0 to 50.0 K
0.1 K
Winding exponent
1.0 to 2.0
0.1
Time constant
0 to 30 min.
1 min.
2
Technical Data