8I20 15
OPERATION
CURRENT LOOP TUNING
The 8I20 has settable tuning parameters for its PI current control loop. The
parameters are KQP, KDP, KQI, and KDI. KQP and KDP are the Proportional terms and
KQI and KDI are the Integral terms. Normally KQP should equal KDP and KQI should
equal KDI. The Startup values of KQP, KDP, KQI, and KDI are set by the cooresponding
EEPROM parameters NVKQP, NVKDP, NVKQI, and NVKDI. Default values forNV KQP
and NVKDP are 50 and default values for NVKQI and NVKDI are 150000. These defaults
are suitable for a large range of motors, but may need to be changed to optimize current
loop operation for specific motors.