Merlin CO2 Monitor   

 

 

 

 

 

                          User Guide 

 

 

Rev: 1  05-19

 

5  

2.6

 

0-10 Volt DC Output  

The voltage will increase / decrease depending on the ppm read out of Co2 detected.  
 

Model: 2800ppm Analogue output 

Model: 4500ppm Analogue output 

ppm 

Voltage 

ppm 

Voltage 

0-1000 

0-500 

1000-1500 

500-750 

1500-2000 

750-1000 

2000-2800 

1000-1250 

2800+ 

10 

1250-1500 

Model: 1500ppm Analogue output 

1500-1750 

2V per 1000ppm 

1750-2000 

2000-2400 

2400-2800 

10 

 
2.7

 

Audible Alarm  

There is a switch on the circuit board to activate/de-activate the audible 

alarm.  

 
ON = audible alarm on (default). 
1 = audible alarm off. 

 

 LED Indication Status  

 

Model: CO2 Monitor 1500ppm 

 

Low (Green) LED 

Good air quality, CO

2

 <900ppm 

 

Medium (Amber) LED 

Moderate air quality, 900ppm> CO

2

 <1200ppm 

 

High (Red) LED 

Poor air quality CO

2

 >1200ppm 

 
Model: CO2 Monitor 2800ppm 

 

Low (Green) LED 

Good air quality, CO

2

 <1000ppm 

 

Medium (Amber) LED 

Moderate air quality, 1000ppm> CO

2

 <1500ppm 

 

High (Red) LED 

Poor air quality CO

2

 >1500ppm 

 

 
 
 

Summary of Contents for CO2 Monitor 1500 ppm

Page 1: ...Merlin CO2 Monitor User Guide Rev 1 05 19 1 Gas Safety Products Merlin CO2 Monitor 1500 2800 4500 ppm User Guide Please read this guide carefully and retain for future use...

Page 2: ...nstallation Operation 4 2 1 Mounting the CO2 Monitor 4 2 2 Mains Supply 4 2 3 Alarm Relay 4 2 4 Pre Alarm Relay 4 2 5 Temperature Relay 4 2 6 0 10 Volt DC Output 5 2 7 Audible Alarm 5 3 LED Indication...

Page 3: ...nsor element is 10 Years Do not apply lighter gas or other aerosols to the detector this will cause extreme damage Never ignore your device when in alarm This device requires a continual supply of ele...

Page 4: ...e above 2800ppm and automatically switch back once the levels have dropped below 2750ppm Model CO2 Monitor 4500ppm This will switch over should the level of Co2 rise above 4500ppm and automatically sw...

Page 5: ...500 1750 7 2V per 1000ppm 1750 2000 8 2000 2400 9 2400 2800 10 2 7 Audible Alarm There is a switch on the circuit board to activate de activate the audible alarm ON audible alarm on default 1 audible...

Page 6: ...ppm 4 Specification Power Supply 110 120VAC 50Hz Max 2VA Gas Sensor Carbon Dioxide Non Dispersive Infrared Detector NDIR ABC Logic Self Calibration CO2 Measuring Range 0 9999ppm Resolution 1ppm Accura...

Page 7: ...High and low voltage wires should not be run in the same conduit 6 Maintenance To keep your device in good working order you must follow these steps DO carefully remove any accumulated dust from the o...

Page 8: ...ove warranty period In no event shall the manufacturer be liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the co...

Reviews: