shunt trip-
u ndervoltage
trip device
[!]
ensure that b reaker is
discharged or trip it by pushing the
red trip button
A
remove the screws
8
and open
front cover
m
shunt trip and undervoltage
tnp must be 1nstalled in left s1de
ONLY
I1J
when the breaker is operated
by a rotary operating handle, the
accessory is latched by another
leaf spring
W
slide the upper side of the
accessory below the plastic hook
1n such a position that you have
the wire fixing screws facing you
Push down the lower side stra1ght
down until it is latched by the leaf
spring
i
I
electrical data
shunt trip
catalog voltage
inrush
number
current
36437
60Hz 120V
2.5A
36446
240V
0.3A
36446
480V
0.5A
36447
600V
1A
36434 DC
12V
3.8A
36435
24V
11
A
36436
48V
S.SA
36437
125V
2.5A
------------- � ..
undervoltage trip
catalog voltage
sealed-in
number
current
36418
60Hz 120V
OOSOA
36419
240V
0.020A
36420
480V
0.014A
36421
600V
0.010A
36410
DC
24V
0 037A
36411
48V
0.022A
36412
125V
0.014A
'\
/
��
9
www
. ElectricalPartManuals