mcr ZIPP
fire protection shut-off valve
MERCOR SA –
The company reserves the right to modify and change the document. Version 20.10.20.5
10/14
INSTALLATION IN THE CEILING_______________________________________________________________
Figure 11. Sample method of installation for the mcr ZIPP valve in the ceiling
NOTE
During the installation of a mcr ZIPP, pay particular attention so that the thermal release (fuse element) do not get
damaged, do not expose it to high temperature (fire, welders, soldering irons) that cause its activation (it is a single
use element and is not subject to warranty replacement).
1- Connection stub pipe
2 – e.g. gypsum plaster or mortar
3 – Concrete ceiling
4 – Extension stub pipe
5 – ventilation duct
X – wall thickness