background image

mcr FID S/… c/P

 single-plane fire dampers 

„MERCOR” SA – 

The company reserves the right to modify and change the document

 

4/18 

place  where  the  insulation  is  performed,  there  is  a  swelling  gasket.  The  sealing  at  the  partition  circumference  is 
effected by a rubber gasket installed on the partition.

 

The enclosure is ended from both ends with flange connections. 

 

Action

  

The  principle  of  action  and  behaviour  of  single-plane  dampers  mcr  FID  S/…  c/P  depends  on  the  version  of  their 
application: 

    

   

 

shut-off fire dampers – mcr FID S/S c/P 

In normal operating position, the dampers are open. Closing the dampers (safety position) takes place: 

   

 

   

 

automatically, by activation of the thermoelectric release 

   

 

   

 

manually, by pressing the control button at the thermoelectric release 

   

 

   

 

remotely, by activation of an electric axial actuator with a return spring, as a result of removing 

   its supply voltage 

   

 

   

 

automatically, by activation of the thermal release and the actuation spring 

        

shut-off fire dampers for fire ventilation systems – mcr FID S/V c/P 

In normal operating position, the dampers are closed. Opening the dampers (safety position) takes place: 

   

 

    

remotely, by activation of an electric axial actuator without a return spring, as a result of applying 

   the supply voltage to the actuator in the right manner 

   

 

    

remotely, by activation of the electromagnetic release and a spring as a result of applying the voltage 

        

shut-off fire dampers for mixed fire ventilation systems – mcr FID S/V-M c/P

 

In normal operation dampers are closed or open, depending on the function carried out. Opening/closing the 
dampers (safety position) takes place: 

   

 

    

remotely, by activation of the electrical axial actuator without a return spring in order to apply supply  

        voltage to the actuator in the right manner 

        

transfer fire dampers – mcr FID S/T c/P

 

In normal operating position, the dampers are open. Closing the dampers (safety position) takes place: 

   

 

    

automatically, by activation of the thermoelectric release 

   

 

    

manually, by pressing the control button at the thermoelectric release 

   

 

    

remotely, by activation of an electric axial actuator with a return spring, as a result of removing  

    its supply voltage 

   

 

    

automatically, by activation of the thermal release and the actuation spring 

        

relief fire dampers – mcr FID S/G c/P 

In normal operating position, the dampers are open. Closing the dampers (safety position) takes place: 

   

 

    

remotely, by activation of an electric axial actuator with a return spring, as a result of removing  

   its supply voltage The actuator has no thermoelectric release. 

 
It  is  possible  to  check  the  correctness  of  damper  co-operation  with  an  electrical  actuator  manually,  for  service 
purposes using a special hex wrench placed in the socket marked on the actuator, and rotated to set the damper 
partition in the relevant position. Wrench rotation should be done evenly, slowly and carefully. Too quick or too rapid 
rotation  of  the  key  may  cause  damage  of  the  internal  actuator  mechanism,  or  damage  of  the  drive  transmission 
system. 
In the integrated version it is possible to check the correctness of damper co-operation with a release and control 
manually, for service purposes by pressing a lever on the mechanism. 

 

NOTE 
In any case it is forbidden to pull directly by the damper partition in order to open or close 
it. Such an action may cause damage of the devices' self-braking drive mechanism and is 
not covered by the warranty.  
It  is  recommended  that  the  fire  damper  were  opened  and  closed  when  the  ventilation 
system is turned off. 

 

 

 

Summary of Contents for mcr FID S c/P Series

Page 1: ...l Grzegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 0 58 341 39 85 OPERATION AND MAINTENANCE MANUAL Fire damper type mcr FID S c P Version FID C 19 11 27 9 FIRE VENTILATION SYSTEMS DEPARTMENT ...

Page 2: ... INTENDED USE 3 4 DEVICE DESIGN AND PRINCIPLE OF OPERATION 4 5 DEVICE LABELLING 5 6 DEVICE ASSEMBLY 6 6 1 INSPECTION BEFORE THE ASSEMBLY 6 6 2 FIXING HOLE 7 6 3 EMBEDDING 7 6 4 ELECTRICAL CONNECTIONS 11 7 TRANSPORT AND STORAGE CONDITIONS 16 8 MAINTENANCE AND SERVICE 16 9 WARRANTY CONDITIONS 16 Labelling used in the operation and maintenance manual Option available Option unavailable ...

Page 3: ... dust except for when they are included in a special individually developed programme of service and technical inspections Fire resistance Damper type mcr FID S S c P have the fire resistance of EI60S S V M T G EI120S S V M T G EI60 S V M T G EI120 S V M T G E60S S V M T G E120S S V M T G E60 S V M T G E120 S V M T G depending on application method and place of installation of the damper Performan...

Page 4: ...l axial actuator without a return spring in order to apply supply voltage to the actuator in the right manner transfer fire dampers mcr FID S T c P In normal operating position the dampers are open Closing the dampers safety position takes place automatically by activation of the thermoelectric release manually by pressing the control button at the thermoelectric release remotely by activation of ...

Page 5: ...T S V M T G EXBF 230 S V M T G BFN 230 T S V M T G EXBF 24 S V M T G BFN 24 T ST S V M T G BF 24 TN TL S V M T G A spring mechanism RST S V M T G RST KW1 S S V M T G RST KW1 24P S V M T G RST KW1 24I S V M T G RST KW1 230P S V M T G RST KW1 230I S V M T G Main dimensions Gear A C D E BFN 157 30 75 57 BFL 138 30 75 53 BF 24TL ST 198 10 75 65 EXBF 225 55 75 175 embedding border mcr FID S c P fire da...

Page 6: ...dampers sets multiple damper sets The mcr FID S c P shut off dampers may also be installed in partitions with a lower class of fire resistance In case of such an installation dampers have fire protection equal to the fire protection of the partition maintaining the smoke tightness criteria In the case of installing the damper in a specific type of wall with thickness lower than required locally in...

Page 7: ...llide with the enclosure elements etc Close the damper partition Carefully fill the gap between the damper casing and the wall with the right mortar that ensures wall and damper fire resistance taking particular attention so that it does not get on the acting elements release and control mechanism partition gaskets limits To ensure it it is mandatory to secure the damper with film or any other cov...

Page 8: ...side of the damper is unacceptable After connecting the ventilation duct check the correctness of damper operation again During the installation of a mcr FID S c P damper pay particular attention so that the thermal release fuse element do not get damaged do not expose it to high temperature fire welders soldering irons that cause its activation it is a single use element and is not subject to war...

Page 9: ...l from concrete blocks or full bricks 6 Temperature resistant gasket 7 A section embedding border X wall thickness Installation of the FID S c P damper in a concrete block or full brick walls 1 Ventilation duct 2 Sheet metal screw ST4 2x16 3 Damper mcr FID S S c P BxH 4 E g cement mortar 5 Ceiling 6 Temperature resistant gasket 7 A section embedding border X Wall thickness Installation of a FID S ...

Page 10: ...mcr FID S c P damper in a panel wall 1 e g a masonry wall 2 A building element with fire resistance equal or higher to the building envelope resistance 3 mcr FID S p P fire damper BxH 4 A building element with fire resistance equal or higher to the building envelope resistance For example a brick wall 5 e g mortar Installation of the mcr FID S c P fire damper as a multiple damper set a set of 4 Ot...

Page 11: ...ivation position degrees 5 80 5 80 Torque motor 18 Nm 18 Nm spring 12 Nm 12 Nm Cable connection motor L 0 9 m 2x0 75 mm2 2x0 75 mm2 auxiliary circuit breaker 6x0 75 mm2 6x0 75 mm2 Movement time 0 90 motor 120 s 120 s return spring 16 s 16 s Operating temperature range 30 50 C 30 50 C Sound pressure level motor max 45 dB A max 45 dB A spring 63 dB A 63 dB A Technical specifications Actuators BE24 B...

Page 12: ... data actuators BFL24 BFL24 T BFL230 BFL230 T BFN24 BFN24 T BFN230 BFN230 T Power supply AC 24 V 50 60 Hz DC 24 V AC 220 240 V 50 60 Hz AC 24 V 50 60 Hz DC 24 V AC 220 240V 50 60 Hz Power demand when putting the spring under tension when in standby 2 5 W 0 7 W 3 5 W 1 1 W 4 W 1 4 W 5 W 2 1 W Apparent power 4 VA 6 5 VA 6 VA 10 VA Protection class III II III II IP rating IP 54 IP 54 IP 54 IP 54 auxi...

Page 13: ...he right to modify and change the document 13 18 Connection diagram for the BFL24 T BFL230 T BFN24 T BFN230 T BF24 TN and BF230 TN actuators Connection diagram for the BE24 BLE24 BE230 and BLE230 actuators Connection diagram for the BEE24 BEN24 BEE230 and BEN230 actuators ...

Page 14: ...DT 6A 3 max 250 V AC 2 x SPDT 6A 3 max 250 V AC activation position 5 80 5 80 Torque motor 18 Nm 18 Nm spring 12 Nm 12 Nm Movement time 90 motor 150 s 150 s return spring 20s 20s Ambient temperature 20 50 C 20 50 C Connection diagram for the EXBF actuators Caution For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 10...

Page 15: ...tion diagram for transformer module type MP230 24 Warning Location of limit switches of the mechanism was shown for the damper safety position For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 2 or 230V 2 Power supply devices other than listed above may cause malfunction and will not be covered by the warranty condi...

Page 16: ...ng and installing support the damper on the sides or edges of the body Dampers should be stored in closed rooms that provide protection against external weather conditions In the case dampers are stored on the ground place them on protection pads in order to protect them against damage 8 MAINTENANCE AND SERVICE Mercor SA devices should undergo periodical technical inspections and maintenance actio...

Page 17: ...6 The warranty liability only covers all defects arising from causes present in the equipment at the date of sale 7 Defects caused by improper operation or otherwise as listed in Item 10 herein the buyer warranty beneficiary will be charged with the costs of their removal 8 Condition for rectifying defects is that the applicant makes the site localisation where devices are installed available in p...

Page 18: ...hereof with removed or damaged nameplate rating plate and or warranty seals 11 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance in accordance with the section MAINTENANCE AND SERVICING in the following Operating and Maintenance Manual 12 This warranty shall be made immediately void and null if The buyer warranty right...

Reviews:

Related manuals for mcr FID S c/P Series