mcr FID S/… c/P

 single-plane fire dampers 

„MERCOR” SA – 

The company reserves the right to modify and change the document

 

3/18 

NOTE 

With the date of publication of the operation and maintenance manual, the previous 

versions are no longer valid. 

The operation and maintenance manual does not concern the dampers manufactured 

before the date of its publication. 

1. INTRODUCTION 

The purpose of this operation and maintenance manual is to get the user acquainted with the intended use, design, 
the principle of operation, correct installation and operation of the product. 
The manual also includes additional information about the operating conditions, maintenance and warranty conditions 
of the product. 
 

2. THE SUBJECT OF THE MANUAL   

This  manual  concerns  the  entire  group  of  single-plane  fire  dampers  type  mcr  FID  S/…  c/P.  Observing 
recommendations included in the manual ensures correct function of the device in terms of fire protection of rooms 
as well as safety of the system users. 
 

3. DEVICE INTENDED USE 

  

 

Application 

Single-plane fire dampers type mcr FID S/… c/P may be used: 

   

 as shut-off fire dampers – mcr FID S/S c/P 

    as shut-off fire dampers for fire ventilation systems – mcr FID S/V c/P 

   

 as shut-off fire dampers for mixed fire ventilation systems – mcr FID S/M c/P 

    as transfer dampers – mcr FID S/T c/P 
    as relief dampers – mcr FID S/G c/P 

 
The dampers may not work in systems exposed to dust, except for when they are included in a special, individually 
developed programme of service and technical inspections. 
 

Fire resistance 

Damper type mcr 

FID S/S c/P

 have the fire resistance of: 

  EI60S 

  /S    /V    /M    /T    /G   

 

EI120S 

 

/S    /V    /M    /T    /G 

  EI60 

  /S    /V    /M    /T    /G   

 

EI120 

 

/S    /V    /M    /T    /G 

  E60S 

  /S    /V    /M    /T    /G   

 

E120S 

 

/S    /V    /M    /T    /G 

  E60 

  /S    /V    /M    /T    /G   

 

E120 

 

/S    /V    /M    /T    /G 

depending on application, method and place of installation of the damper. 

 

Performance versions

  

Dampers mcr FID S/… c/P may be performed as: 

    

   

Rectangular dampers 

    

   

Rectangular dampers with round connections 

   

    Round dampers  

  

Dimension type series

  

Dampers mcr FID S/S c/P are performed in the following dimensions: 

Width: between 200 and 1000 mm 
Height: between 200 and 800 mm 
Width: between 296 and 390 mm 

Apart from the standard dimensions there is a possibility of performing dampers with intermediate dimensions. The 
maximum surface of dampers of type mcr FID S/S c/P equals: 0.8 m

2

. The minimum surface of the dampers equals 

0.04 m

2

.  

 

 

 

4. DEVICE DESIGN AND PRINCIPLE OF OPERATION 

 

Design

  

The single-plane dampers mcr FID S/… c/P are made of an enclosure with a rectangular cross-section, a portable 
shut-off partition and a release and control mechanism activated manually or automatically after the thermal release 
is activated. The damper enclosure is made of a steel, galvanised steel sheet, or a stainless steel one. In the damper 
enclosure, on its circumference, the insulation perforation with the relevant width is performed. The shut-off partition 
of dampers is made of a non-flammable plate and is set in a sheet reinforcement profile. On the enclosure, in the 

Summary of Contents for mcr FID S c/P Series

Page 1: ...l Grzegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 0 58 341 39 85 OPERATION AND MAINTENANCE MANUAL Fire damper type mcr FID S c P Version FID C 19 11 27 9 FIRE VENTILATION SYSTEMS DEPARTMENT ...

Page 2: ... INTENDED USE 3 4 DEVICE DESIGN AND PRINCIPLE OF OPERATION 4 5 DEVICE LABELLING 5 6 DEVICE ASSEMBLY 6 6 1 INSPECTION BEFORE THE ASSEMBLY 6 6 2 FIXING HOLE 7 6 3 EMBEDDING 7 6 4 ELECTRICAL CONNECTIONS 11 7 TRANSPORT AND STORAGE CONDITIONS 16 8 MAINTENANCE AND SERVICE 16 9 WARRANTY CONDITIONS 16 Labelling used in the operation and maintenance manual Option available Option unavailable ...

Page 3: ... dust except for when they are included in a special individually developed programme of service and technical inspections Fire resistance Damper type mcr FID S S c P have the fire resistance of EI60S S V M T G EI120S S V M T G EI60 S V M T G EI120 S V M T G E60S S V M T G E120S S V M T G E60 S V M T G E120 S V M T G depending on application method and place of installation of the damper Performan...

Page 4: ...l axial actuator without a return spring in order to apply supply voltage to the actuator in the right manner transfer fire dampers mcr FID S T c P In normal operating position the dampers are open Closing the dampers safety position takes place automatically by activation of the thermoelectric release manually by pressing the control button at the thermoelectric release remotely by activation of ...

Page 5: ...T S V M T G EXBF 230 S V M T G BFN 230 T S V M T G EXBF 24 S V M T G BFN 24 T ST S V M T G BF 24 TN TL S V M T G A spring mechanism RST S V M T G RST KW1 S S V M T G RST KW1 24P S V M T G RST KW1 24I S V M T G RST KW1 230P S V M T G RST KW1 230I S V M T G Main dimensions Gear A C D E BFN 157 30 75 57 BFL 138 30 75 53 BF 24TL ST 198 10 75 65 EXBF 225 55 75 175 embedding border mcr FID S c P fire da...

Page 6: ...dampers sets multiple damper sets The mcr FID S c P shut off dampers may also be installed in partitions with a lower class of fire resistance In case of such an installation dampers have fire protection equal to the fire protection of the partition maintaining the smoke tightness criteria In the case of installing the damper in a specific type of wall with thickness lower than required locally in...

Page 7: ...llide with the enclosure elements etc Close the damper partition Carefully fill the gap between the damper casing and the wall with the right mortar that ensures wall and damper fire resistance taking particular attention so that it does not get on the acting elements release and control mechanism partition gaskets limits To ensure it it is mandatory to secure the damper with film or any other cov...

Page 8: ...side of the damper is unacceptable After connecting the ventilation duct check the correctness of damper operation again During the installation of a mcr FID S c P damper pay particular attention so that the thermal release fuse element do not get damaged do not expose it to high temperature fire welders soldering irons that cause its activation it is a single use element and is not subject to war...

Page 9: ...l from concrete blocks or full bricks 6 Temperature resistant gasket 7 A section embedding border X wall thickness Installation of the FID S c P damper in a concrete block or full brick walls 1 Ventilation duct 2 Sheet metal screw ST4 2x16 3 Damper mcr FID S S c P BxH 4 E g cement mortar 5 Ceiling 6 Temperature resistant gasket 7 A section embedding border X Wall thickness Installation of a FID S ...

Page 10: ...mcr FID S c P damper in a panel wall 1 e g a masonry wall 2 A building element with fire resistance equal or higher to the building envelope resistance 3 mcr FID S p P fire damper BxH 4 A building element with fire resistance equal or higher to the building envelope resistance For example a brick wall 5 e g mortar Installation of the mcr FID S c P fire damper as a multiple damper set a set of 4 Ot...

Page 11: ...ivation position degrees 5 80 5 80 Torque motor 18 Nm 18 Nm spring 12 Nm 12 Nm Cable connection motor L 0 9 m 2x0 75 mm2 2x0 75 mm2 auxiliary circuit breaker 6x0 75 mm2 6x0 75 mm2 Movement time 0 90 motor 120 s 120 s return spring 16 s 16 s Operating temperature range 30 50 C 30 50 C Sound pressure level motor max 45 dB A max 45 dB A spring 63 dB A 63 dB A Technical specifications Actuators BE24 B...

Page 12: ... data actuators BFL24 BFL24 T BFL230 BFL230 T BFN24 BFN24 T BFN230 BFN230 T Power supply AC 24 V 50 60 Hz DC 24 V AC 220 240 V 50 60 Hz AC 24 V 50 60 Hz DC 24 V AC 220 240V 50 60 Hz Power demand when putting the spring under tension when in standby 2 5 W 0 7 W 3 5 W 1 1 W 4 W 1 4 W 5 W 2 1 W Apparent power 4 VA 6 5 VA 6 VA 10 VA Protection class III II III II IP rating IP 54 IP 54 IP 54 IP 54 auxi...

Page 13: ...he right to modify and change the document 13 18 Connection diagram for the BFL24 T BFL230 T BFN24 T BFN230 T BF24 TN and BF230 TN actuators Connection diagram for the BE24 BLE24 BE230 and BLE230 actuators Connection diagram for the BEE24 BEN24 BEE230 and BEN230 actuators ...

Page 14: ...DT 6A 3 max 250 V AC 2 x SPDT 6A 3 max 250 V AC activation position 5 80 5 80 Torque motor 18 Nm 18 Nm spring 12 Nm 12 Nm Movement time 90 motor 150 s 150 s return spring 20s 20s Ambient temperature 20 50 C 20 50 C Connection diagram for the EXBF actuators Caution For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 10...

Page 15: ...tion diagram for transformer module type MP230 24 Warning Location of limit switches of the mechanism was shown for the damper safety position For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 2 or 230V 2 Power supply devices other than listed above may cause malfunction and will not be covered by the warranty condi...

Page 16: ...ng and installing support the damper on the sides or edges of the body Dampers should be stored in closed rooms that provide protection against external weather conditions In the case dampers are stored on the ground place them on protection pads in order to protect them against damage 8 MAINTENANCE AND SERVICE Mercor SA devices should undergo periodical technical inspections and maintenance actio...

Page 17: ...6 The warranty liability only covers all defects arising from causes present in the equipment at the date of sale 7 Defects caused by improper operation or otherwise as listed in Item 10 herein the buyer warranty beneficiary will be charged with the costs of their removal 8 Condition for rectifying defects is that the applicant makes the site localisation where devices are installed available in p...

Page 18: ...hereof with removed or damaged nameplate rating plate and or warranty seals 11 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance in accordance with the section MAINTENANCE AND SERVICING in the following Operating and Maintenance Manual 12 This warranty shall be made immediately void and null if The buyer warranty right...

Reviews: