mcr FID S/… c/P
single-plane fire dampers
„MERCOR” SA –
The company reserves the right to modify and change the document
3/18
NOTE
With the date of publication of the operation and maintenance manual, the previous
versions are no longer valid.
The operation and maintenance manual does not concern the dampers manufactured
before the date of its publication.
1. INTRODUCTION
The purpose of this operation and maintenance manual is to get the user acquainted with the intended use, design,
the principle of operation, correct installation and operation of the product.
The manual also includes additional information about the operating conditions, maintenance and warranty conditions
of the product.
2. THE SUBJECT OF THE MANUAL
This manual concerns the entire group of single-plane fire dampers type mcr FID S/… c/P. Observing
recommendations included in the manual ensures correct function of the device in terms of fire protection of rooms
as well as safety of the system users.
3. DEVICE INTENDED USE
Application
Single-plane fire dampers type mcr FID S/… c/P may be used:
as shut-off fire dampers – mcr FID S/S c/P
as shut-off fire dampers for fire ventilation systems – mcr FID S/V c/P
as shut-off fire dampers for mixed fire ventilation systems – mcr FID S/M c/P
as transfer dampers – mcr FID S/T c/P
as relief dampers – mcr FID S/G c/P
The dampers may not work in systems exposed to dust, except for when they are included in a special, individually
developed programme of service and technical inspections.
Fire resistance
Damper type mcr
FID S/S c/P
have the fire resistance of:
EI60S
/S /V /M /T /G
EI120S
/S /V /M /T /G
EI60
/S /V /M /T /G
EI120
/S /V /M /T /G
E60S
/S /V /M /T /G
E120S
/S /V /M /T /G
E60
/S /V /M /T /G
E120
/S /V /M /T /G
depending on application, method and place of installation of the damper.
Performance versions
Dampers mcr FID S/… c/P may be performed as:
Rectangular dampers
Rectangular dampers with round connections
Round dampers
Dimension type series
Dampers mcr FID S/S c/P are performed in the following dimensions:
Width: between 200 and 1000 mm
Height: between 200 and 800 mm
Width: between 296 and 390 mm
Apart from the standard dimensions there is a possibility of performing dampers with intermediate dimensions. The
maximum surface of dampers of type mcr FID S/S c/P equals: 0.8 m
2
. The minimum surface of the dampers equals
0.04 m
2
.
4. DEVICE DESIGN AND PRINCIPLE OF OPERATION
Design
The single-plane dampers mcr FID S/… c/P are made of an enclosure with a rectangular cross-section, a portable
shut-off partition and a release and control mechanism activated manually or automatically after the thermal release
is activated. The damper enclosure is made of a steel, galvanised steel sheet, or a stainless steel one. In the damper
enclosure, on its circumference, the insulation perforation with the relevant width is performed. The shut-off partition
of dampers is made of a non-flammable plate and is set in a sheet reinforcement profile. On the enclosure, in the