Menu
Item
Default
Set At
Description
PSF
AUtO
Pump Seal Failure controller action
(selectable automatic or manual reset)
TESt
On
System Test (Selectable on or off)
PrSt
On
Pump Run Time Rest (Selectable on or off)
SPH
23.1
Set Point High value (default is in feet)
SPL
0.0
Set Point Low value (default is in feet)
S1PI
OFF
Set Point 1 Power Interrupt
(selectable on or off)
S1IH
OFF
Set Point 1 Inhibit (selectable on or off)
S2PI
OFF
Set Point 2 Power Interrupt
(selectable on or off)
Set Point 2 Inhibit (selectable on or off)
Setpoint 2 (selectable 0 to 60) Time Delay
Peak, highest input value seen since last reset
Valley, lowest input value seen since last reset
Alarm 1 Function (selectable off, lo, hi, hilo, sf, ot, or sfot)
Alarm Type 1 (selectable abs (absolute)
or de (deviation))
A1rE
OnOf
Alarm 1 Reset (selectable onof (auto)
or hold (manual))
Secure
A1Pi
OFF
Alarm 1 Power Interrupt (selectable on or off)
A1iH
OFF
Alarm 1 Inhibit (selectable on or off)
A1St
CLOS
Alarm 1 Output State (selectable close
or open)
A1LP
O On
Alarm 1 Lamp condition when contact
is closed (selectable on or off)
A1td
OFF
Alarm 1 Time Delay (selectable off or 1
to 8000 seconds)
AL2
Lo
Alarm 2 function ( selectable off, lo, hi, hilo, sf, ot, or sfot)
A2t
AbS
Alarm 2 Type (selectable abs (absolute)
or de (deviation))
A2rE
OnOf
Alarm 2 Reset (selectable onof (auto) or
hold (manual))
A2Pi
OFF
Alarm 2 Power Interrupt (selectable on or off)
A2iH
OFF
Alarm 2 Inhibit (selectable on or off)
A2St
CLOS
Alarm 2 Output State (selectable close or open)
A2LP
O On
Alarm 2 Lamp condition when contact is
closed (selectable on or off)
A2td
OFF
Alarm 2 Time Delay (selectable Off or 1 to
8000 seconds)
Filt
3
Digital Filter
POH 23.1
Process Output High (default is in feet)
27
Men
Sec
L-20:L-20 9/30/10 11:09 AM Page 27