PROGRAMMING CHART
Use the charts on this and the next page to record the values in your application. You may
want to photocopy the pages if you plan to make programming changes.
Menu
Item
Default
Set At
Description
Primary
PV SP1H
XXXX
Home Position, Process Variable &
SP1H's Value displayed
Menu
Item
Default
Set At
Description
SP1H 23.1
Set Point 1 value (default is in feet)
SP1L 0.0
Set Point 1 off value (default is in feet)
SP2H 23.1
Set Point 2 value (default is in feet)
SP2L 0.0
Set Point 2 off value (default is in feet)
A1Hi 23.1
Alarm 1 (high) value (default is in feet)
A2Lo 2.0
Alarm 2 (low) value (default is in feet)
SFS1
120
Pump 1 Seal Failure Set Point
Secondary
SFS2
120
Pump 2 Seal Failure Set Point
P1rn
XXXX
Total ON Time for Pump 1 in HOURS
since last reset
P2rn
XXXX
Total ON Time for Pump 2 in HOURS
since last reset
P1SF
----
Pump 1 Reset for Seal Failure (---- or FAIL)
P2SF
----
Pump 2 Reset for Seal Failure (---- or FAIL)
P1OT
----
Pump 1 Reset for Over Temperature
(---- or FAIL)
P2OT
----
Pump 2 Reset for Over Temperature
(---- or FAIL)
Menu
Item
Default
Set At
Description
SECr
4
Security Selection
SCAH
23.1
Scale High value (default is in feet)
SCAL
0.0
Scale Low value (default is in feet)
dPt
0.0
Decimal Point Positioning
S1St
POut
Set Point 1 State (selectable POut
(Pumping Out) or PIn (Pumping In))
Secure
S2St
POut
Set Point 2 State (selectable POut
(Pumping Out), PIn (Pumping In), or off)
LdLg
On
Lead/Lag (selectable on or off)
InPC
0.0
Input Correction
OSUP
On
Zero Suppression (selectable on or off)
InP
Curr
Input (selectable current or voltage)
POT
AUtO
Pump Over Temperature controller action
(selectable automatic or manual reset)
26
L-20:L-20 9/30/10 11:09 AM Page 26