4.3 Connecting the module to the inverter
1
2
4.3.1 Positive terminal and protective earth
(1) Srcew the protective earth into the upper energy storage
module.
(2)InserttheHVcable(25 mm²,positiveterminal)intothe
positive terminal on the upper energy storage module’s
feed-through terminal block and screw it tight (tightening
torqueof4–4.5 Nm).
•ProtectiveearthandHVcable(25 mm²,positivetermi-
nal) for inverter now now connected.
This steps described in this section refer to the wiring for the Mercedes-Benz Energy Storage Home only. In order to connect
the inverter, please refer to the installation instructions provided with your specific inverter.
The positive terminal on the feed-through terminal block is
markedwith‘
+
’.
Note that the cables to the inverter must be at-
tached to the wall in order to relieve the strain on it!
4.2.4 Communication link
(1) Insert the RJ45 cable into the upper RJ45 connection
socket on the bottom energy storage module.
(2) Insert the other end of the same cable into the lower RJ45
connection socket on the energy storage module above.
(3) Repeat the process until all the energy storage modules are
connected with each other via RJ45 cables.
(4) Insert the RJ45 terminating resistor into the lowest free
RJ45 connection socket on the bottom energy storage
module.
•Communicationlinkconnected.
The RJ45 connection sockets on the energy storage system
are each marked, the upper socket with ‘CoN2’ and the
lower socket with ‘CoN3’.
2
1
4
3
3
17
Mercedes-Benz Energy Storage Home Manual
| Installation