background image

MERak

 

 

MMk-656

 

 

Compact Emergency Telephone for Lifts

 

Rev. M1.5 – S2.5 

©

 MERak. All rights reserved 

Instruction and Connection Manual 

 

10 of 20 

 

Connect the lead-acid battery at 

J2 B+

 (battery 12 Vdc) and 

J2 B-

 (battery GND). 

In  this  way,  the  set  assumes  responsibility  for  charging  the  battery  and  performs 

measurement of the charge remaining. If desired, the set can generate automatic calls to the 
maintenance company for the installation, in the event that the battery tension falls below the 

threshold  programmable  by  the  user  (as  required  by  the  standard  EN.  81-28),  or  is 
disconnected.  

Programming the 

*08#

 register, the telephone will make these automatic calls in these 

cases. To deactivate the calls, it is only necessary to deprogramme the same register. 

If  the  supply  equipment  recommended  by  MERak  is  not  used,  a  stable  and  regulated 

source  should  be  used,  which  should  be  located  as  close  as  possible  to  the  set  to  avoid  the 

possible introduction of electromagnetic parasites in a long supply cable. 

If  it  is  not  desired  to  use  an  emergency  battery  exclusively  for  the  telephone 

(at  the 

responsibility of the installing company)

 but grid power only, this should be connected at the 

terminals provided for the supply 

J2 V+

 and 

J2 V-

WARNING!

 NEVER connect the mains supply to the battery terminals. 

 

7.3.

 

RS-485 serial communications connector (J3) 

Communication  with  the  control  system  or  other  devices  such  as  the  graphical  viewer 

may be carried out via the 

J3 

connector, which is an RS-485 interface. For more information see 

chapter 15. 

The  transmission  speed,  the  number  of  bytes  and  parity  can  be  modified  according  to 

the needs of the equipment where it is connected, but only by means of programming with the 

software 

serviLift,

  available  at  the  MERak  website  (www.merakeurope.com).  A  more  detailed 

explanation of how this bus functions can be found in the 

PC Mode Commands Manual

, available 

on MERak website. 

 

7.4.

 

Telephone line (J4) 

To connect the set to a phone line, the 

J4.1

 and 

J4.3

 terminals should be used. This must 

always be an analogue line. 

Connection of the earth terminal 

J4.2

 denoted 

,  is used to protect the equipment from 

high energy transients in the telephone lines caused by storms and similar phenomena. If the 
connection to earth is omitted, the protection devices provided will  be totally ineffective. The 

equipment will work just the same in this case, but the probability of faults rises considerably. 

MERak strongly recommends the use of this earth connection

It  is  not  recommended  to  use  the  emergency  telephone  connected  to  an  exchange 

because in the event of a power failure, availability of the telephone line is not guaranteed. 

 

Summary of Contents for MMk-656

Page 1: ...INSTRUCTION AND CONNECTION MANUAL MMk 656 Compact Emergency Telephone for Lifts...

Page 2: ...prohibited Disclaimer The manufacturer declines any responsibility to the purchaser of this product and third parties for damages losses costs or work done due to accidents product misuse improper ins...

Page 3: ...TEST CALL EN 81 28 8 5 CLEARING AN ALARM EN 81 28 8 6 ALARM FILTERING EN 81 28 8 7 CONNECTORS 9 7 1 Switches J1 9 7 2 Power supply J2 9 7 3 RS 485 serial communications connector J3 10 7 4 Telephone...

Page 4: ...ally designed for lifts though any terminal at all ought to work This telephone permits programming of the set using its keypad guided by voice assistance MULTI CABIN Several modules up to the maximum...

Page 5: ...e as follows Automatic calling of up to 4 pre programmed numbers when an alarm is raised Automatic calling when a maintenance alarm is raised need to rescue operators or communicate with the centre Pe...

Page 6: ...dvice Possibility of interconnecting up to 4 sets on the same telephone line with no need for extra cabling Flush mounting in the panel with M6 through screws or using double sided adhesive Different...

Page 7: ...onnector Following an audible countdown in the car a call to the first number in the bank of registers dedicated to storage of alarm telephone numbers bank of registers 02 to 05 is initiated If commun...

Page 8: ...so programmed that when the equipment initiates a test call it configures itself to make the following call 24 hours later but should communication be correctly established with the server which atte...

Page 9: ...alarm for the operators which generates a call to the number stored in register 01 of the telephone memories can be connected This possibility is included so that maintenance personnel have a direct...

Page 10: ...V WARNING NEVER connect the mains supply to the battery terminals 7 3 RS 485 serial communications connector J3 Communication with the control system or other devices such as the graphical viewer may...

Page 11: ...o have a point for audio and alarm generation alternative to that of the main unit Interconnection with this external module is by means of the RJ 45 terminals J6 For this a male male RJ 46 cable shou...

Page 12: ...rwritten by those from the SD card The set plays a message confirming that it has been updated The file CONFIG CFG is not found on the SD card One is created on the SD card using the previous paramete...

Page 13: ...ured as in the following table Cabin 1 Cabin 2 Cabin 3 Cabin 4 Switch 3 ON OFF ON OFF Switch 4 ON ON OFF OFF Table 1 Car selection switches 8 STATUS LED General status information for the equipment is...

Page 14: ...eter programming and for playing the car announcements In the case of playing car messages up to 4 different languages can be selected to be played consecutively For example the countdown message play...

Page 15: ...ll NOT be possible to receive incoming calls If two cars are programmed with the same number it will NOT be possible to communicate between them and so neither will it be possible to reconfigure them...

Page 16: ...easurement cycle To do this it is necessary to issue the command 91 or its equivalent in PC mode Once this command has been entered and the programming process has been completed hang up the intercom...

Page 17: ...ration 3 Wiring diagram for the MMk 656 15 RS 485 SERIES CHANNEL The J3 input corresponds to an RS 485 series channel The port configuration is 9 data bits without parity and one Stop bit 9N1 at 4800b...

Page 18: ...t of frame Data Includes the code of the commands and the data necessary for their execution CHK Checksum of 7 bits of the field Data Calculation of the XOR of all the bytes of the frame except STX an...

Page 19: ...These are the messages which it is desired to reproduce in the module of the lift car and they are generated from the combination of messages in the following table Sint 1 Message Sint 1 Message Sint...

Page 20: ...ice message table Messages are formed by combining a message from each of the columns For instance to build the phrase Floor One choose Floor from the first column Silence from the second and One from...

Reviews: