85-03-01107
FV34 DECOR
Page
21
Rough Framing Dimensions
The Rough Framing Dimensions must be
maintained to allow this fireplace to slide into
the framing cavity.
SPECIAL FRAMING NOTE: On the left side of
this unit, a metal box containing the ignition
system protrudes outward ½” and an electrical
cable clamp protrudes outward 1-
1/4”.
If the fireplace is to be recessed in a cavity deeper than 14-
5/8”, all framing and finishing materials protruding past the
front face of this fireplace must be of the NON-COMBUSTIBLE variety.
Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose this fireplace and its vent system. Vertical vents that run on the outside
of a building may be, but are not required to be, installed inside a chase.
Construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of
local building codes. Local building codes
MUST
be adhered to.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase
should not break the outside building envelope in any manner.
Wall, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers should be
installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infiltration may be
an issue, the inside surfaces of the chase may be sheet rocked and taped for maximum air tightness.
To further prevent drafts, the fire stops should be caulked with high temperature caulk to seal the gaps. Gas line holes and
other openings should be caulked with high temp caulk or stuffed with unfaced insulation. If the appliance is being installed on
a cement slab, a layer of plywood may be placed underneath this fireplace to prevent conducting cold up into the room.
Minimum Rough Framing Dimensions
DESCRIPTION
DIMENSION (INCHES)
A
Width
40-5/8
”
B
Height
36-3/4
”
C
Depth
14-
5/8”
D
Vent opening height
10-
3/4”
E
Vent opening width
10-
3/4”
Figure 3-16 FINALIZED FRAMING DIMENSIONS
49-7/8"
FLOOR
TO
WALL
THIMBLE
CENTER
37"
FINALIZED
HEIGHT