85-03-00988
64 |
P a g e
“FIRST TIME” PILOT LIGHTING INSTRUCTIONS
IMPORTANT:
Be sure all items on "INSTALLATION CHECK OFF LIST" in the Installation Manual have been completed!
CAUTION:
If the pilot goes out, be sure to wait a minimum of five minutes before attempting to relight the pilot.
1. Make certain that any manual gas supply shut-off valves located upstream of
fireplace are open and the Master On/Off switch is toggled to the ON position.
2. Make certain that 110VAC power is connected to Electrical Junction Box on left
side of Fireplace and that the Electrical Power is “ON”.
3. Insert Batteries in the Remote Transmitter. Note the polarity of batteries and insert
as indicated on the battery compartment cover.
4. For the “First Time Lighting”, Remove the Glass Door. This is required to purge the
gas line of air and to inspect the pilot lighting spark.
5. Press OFF on the remote Transmitter. Press MODE button on Transmitter. Press
UP for “CPI” (standing pilot mode). Press MODE button again to exit. You will hear
a series of clicks and after a few seconds, you will hear sparking at the pilot spark
electrode.
6. Allow adequate time for the air in the gas-line to purge. The control system will stop
sparking after 30 seconds if the pilot light does not light. After a 30 second delay the control system will start sparking
again for 30 seconds more. If the pilot light does not light after the third 30 second spark event, the system will enter
“Lock-out” mode. To unlock from “Lock-out” mode, Press the ON/OFF button on Transmitter then Press ON/OFF but-
ton on the transmitter again so the Transmitter display turns off. Wait 30 seconds. Turn OFF the Master Switch. Wait
30 seconds and Turn Master Switch ON again. Repeat this sequence until the pilot flame lights and the pilot is burn-
ing steadily.
7.
Once the pilot flame is lit and well-established, close glass door.
WARNING: NEVER IGNITE MAIN BURNERS
WITH GLASS DOOR REMOVED OR OPEN. Doing so will lead to damage to pilot flame sensor and spark elec-
trode wire leads.
8.
Press the ON/OFF button on Transmitter to “ON”. All burners should ignite
and run at “high-fire”. Toggle through other functions of the Fireplace
(Flame Height, Fan Speed and Accent Light brightness) to verify all func-
tions.
9.
Perform gas inlet and outlet pressure tests and leak tests on field installed
gas fittings and factory installed fittings in the gas valve compartment, at
this time. Note: Burners must be ON to check outlet pressures and to leak
test gas train fittings upstream of main gas valve.
INITIALIZING THE REMOTE CONTROL SYSTEM
MASTER SWITCH: Remote Transmitter WILL NOT communicate to receiver
unless the Master Switch is ON. The master switch when OFF disable all
functions and acts as a Master Safety Shutoff Switch.
(Synchronizing Receiver and Transmitter)
Master Switch and Sync Switch are located at the bottom right corner of the
Glass Frame.
1. Toggle Master Switch to ON (pull toward front of unit). Remote Transmitter
WILL NOT communicate to receiver unless the Master Switch is ON.
2. Locate Sync Switch (directly above Master Switch). Press the Sync Button. The
receiver will beep 3 times indicating that it is ready to synchronize with a Re-
mote Transmitter.
3. Push the “ON” key on the Remote Transmitter. The receiver will beep 4 times to
indicate that the Transmitter’s command is accepted and sets to the particular
code of that Transmitter. The system is now initialized.
NOTE
: Once synchronized, the Transmitter and Receivers will communicate per-
manently and no further Synchronizing steps are necessary unless either the
Transmitter or Receiver is replaced.
REMOTE TRANSMITTER
BLUE LCD
DISPLAY
MODE
SELECTION KEY
UP/DOWN
SELECTION KEY
THERMOSTAT
SELECTION KEY
ON/OFF KEY