5
Distance from
Height
Width
Base
WidthTop
plate
Depth
Depth inc
closed air
intake
Collar
size
Rear to
centre flue
collar
Floor to
rear flue
exit
Floor to air
intake
stove
Air intake
adapter
A
B
B1
C
C1
D
E
F
H
H1
575mm
405mm
424mm
370mm
412mm
125mm
128mm
460mm
151mm
100mm
STOVE DIMENSIONS AND CONNECTION MEASUREMENTS
B1
A
E
D
F
H
B
C
C1
Distance to non combustible materials
The stove can be recessed in a suitable sized non - combustible fireplace but a permanent free air gap of at least 50mm
must be left around the sides and top and at least 50mm at the back of the stove to obtain reasonable heat output and for
access to the stove for removal and maintenance. A clearance of 100mm will give a better heat output.
All non - combustible walls closer than 100mm to the stove should be at least 75mm thick. For practical reasons the back
wall of the fireplace recess and the hearth should ideally be made of non -combustible material. When installing a your stove
in a non combustible chamber combustible materials should not be located where the heat dissipating through the walls of
fireplaces or flues could ignite it. Therefore when installing the stove in the presence of combustible materials due account
must be taken of the guidance on the separation of combustible material given in Building Regulations Approved Document
J and also in these stove instructions. The minimum distances to flammable materials are specified on the EN 13240 plate
on the back of the stove
H1