Installation and Basic Operation
Rev 1.4
Mellanox Technologies
24
6. Copper InfiniBand Cable Connecting/Disconnecting
7. Rack Mounting and Servicing
8. Leakage >3.5mA
9. Add GND Connection
10. Installation Codes
11. Interconnection of Units
12. Equipment Installation
Copper InfiniBand cables are heavy and not flexible, as such they should be carefully
attached to or detached from the connectors. Refer to the cable manufacturer for spe-
cial warnings and instructions.
When this product is mounted or serviced in a rack, special precautions must be taken
to ensure that the system remains stable. In general you should fill the rack with equip-
ment starting from the bottom to the top.
WARNING: High leakage current; Earth connection essential before connecting sup-
ply.
Before connecting this device to the power line, the protective earth terminal screws of
this device must be connected to the protective earth in the building installation.
This device must be installed according to the latest version of the country national
electrical codes. For North America, equipment must be installed in accordance to the
applicable requirements in the US National Electrical Code and the Canadian Electri-
cal Code.
Cables for connecting to the unit RS232 and Ethernet Interfaces must be UL certified
type DP-1 or DP-2. (Note- when residing in non LPS circuit)
Overcurrent Protection: A readily accessible Listed branch circuit overcurrent protec-
tive device rated 20 A must be incorporated in the building wiring.
This equipment should be installed, replaced, or serviced only by trained and qualified
personnel.