Technician Settings
Enter technician settings mode:
Adjust the set point temperature to 10ºC or 50ºF.
Press and hold the button for 10 seconds to enter technician settings mode.
“P01” will appear on display.
View objects and make adjustments:
Use the [Mode] button to step forward between different objects (parameters).
Use the [Fan] button to step backward between different objects (parameters).
Press the [On/Off] button to exit technician settings and return to normal display.
If no button is pressed for 60 seconds, the thermostat will automatically exit technician settings and
return to normal display.
Use the
▲
or
▼
buttons to make adjustments when required.
P1 –
Offset for temperature readings calibration
Range: -6…+6°C / -9…+9°F.
Default: 0°C / 0°F.
P2 –
Set point limit for cooling
Range: 5…35°C
/
41…95°F.
Default: 10°C
/
50°F.
P3 –
Set point limit for heating
Range: 5…35°C
/
41…95°F.
Default: 30°C
/
86°F.
Set point limit for cooling
(°F)
(°C)
Set point limit for heating
(°F)
(°C)
Offset for temperature calibration
(°F)
(°C)
Note: The offset will influence both internal
or external sensors.
Note: The thermostat will stop cooling regardless of
the users set-point
Note: The thermostat will stop heating regardless of
the users set-point
- 32 -