35
5.3.6 AUTOMATIC BATTERY TEST SETUP Screen
In addition to being able to run manual battery tests, your UPS has the capability of performing
regularly scheduled automated battery tests. This display allows you to program various parameters
that control when and how these tests are to be performed. Below is a sample display of this screen:
Refer to section 8.4 for suggested settings for these parameters. There are some restraints on how
various values can be programmed. Quick tests must be enabled if Capacity tests are to be enabled.
Capacity tests can not be performed more often than Quick tests. The unit will automatically correct any
discrepancy should you attempt to violate these constraints. After changing one or more of these
parameters, press the <ESCAPE> key on the keypad to save the new parameters and leave the
display. If you press the <SELECT> key while in this display, you will leave the display, but none of the
changes you made will be saved.
0 1 / 1 1 / 9 9
S E L E C T A B L E P A R A M E T E R S
_ 1 6 : 5 2 : 1 1
1 ) M I N O U T P U T V O L T A G E – ( 5 - 2 0 ) % = 1 5
2 ) M A X O U T P U T V O L T A G E + ( 5 - 2 0 ) % = 1 0
3 ) F R E Q U E N C Y R A N G E + / - ( 0 . 5 - 5 ) H Z = 5 . 0
4 ) F R E Q S L E W R A T E ( 0 - 9 9 ) H Z / S E C = 2 5
5 ) W A L K - I N T I M E ( 0 - 1 5 ) S E C O N D S = 1 0
6 ) E X T B A T T E R I E S ( 0 - 5 1 0 ) A M P - H R S = 7 6
S E L E C T I O N : H I T < E S C A P E > T O E X I T
0 1 / 1 1 / 9 9
A U T O B A T T T E S T S E T U P
1 6 : 5 2 : 1 1
Q U I C K T E S T
|
C A P A C I T Y T E S T
1
E N A B L E D ?
1 ) Y E S | 2 ) Y E S
F R E Q U E N C Y
3 ) D A I L Y | 4 ) 4 W E E K S
D U R A T I O N
3 S E C O N D S | 5 ) 1 M I N U T E
F A I L L E V E L
5 0 % | 6 ) 6 0 %
D A Y & H O U R
7 ) M O N D A Y 8 ) 1 4
S E L E C T I O N : H I T < E S C A P E > T O E X I T