Overspeed detection action selection:
0: Decelerate to stop
The drive decelerates to stop according to the deceleration time, and the failure of Er.oSP is reported.
1: Coast to stop
The drive is subject to coast to stop, and the failure of Er.oSP is reported.
2: Continue to run
The drive reports the alarm of AL.oSP and keeps running.
In order to improve the efficiency of the lifting device, at light loads the user wishes the motor to work
above the rated frequency, the deive automatically calculates the current operating frequency of the
motor according to the motor power-torque curve. This function is selected by [P61.09].
0: Disable
1: For uplink
2: For uplink and downlink
When the drive output frequency exceeds the motor rated frequency, power limits come into play. If the
power exceeds [P61.10] or [P61.11] setting value, the drive stops accelerating and maintains the current
speed regardless of whether the acceleration at that time is 0 or not.
Power control acceleration and deceleration rates
0.0~50.00Hz/s2(5.00)
P61.12
Maximum power limit for downlink
00.0~ 100.0%(75.0%)
P61.11
Maximum power limit for uplink
0~ 100.0%(100.0%)
P61.10
Power limit selection
0~2 (1)
P61.09