5
flag
Alarm 1 mode
setting
3652
Alarm
2
mode
setting
3656
Alarm
3
mode
setting
3660
Alarm
4
mode
setting
3664
Alarm dead zone
setting
3668
Alarm delay times
3672
Operation amount
selection at alarm
6727
6728
6729
6730 6731
6732
6733
6734
6735
6736
6737
6738 6739
6740
6741
6742
Operation amount
at the time of
alarm
6759
6760
6761
6762 6763
6764
6765
6766
6767
6768
6769
6770 6771
6772
6773
6774
External input
status
3680
3681
Cold junction
temperature
3620
Module parameter
saving
3684
Module software
version
information
3688
Thermostat
identification
code
3692
System error status word
(
3612
)
Bit status
ON(1)
OFF(0)
Bit0:Error
When any one of b1 ~ b7 is 1, this
flag is 1.
No error
Bit1:Remain
-
-
Bit2:Hardware
malfunction
AD converter or other hardware
failure, all channels AD conversion
stop
The
hardware
is normal
Bit3:Parameter
setting error
When there is an error in the
internal parameters of MTCV, this
flag will become 1.
Data
backup is
normal
Bit4:Cold junction
temperature
compensation error
Cold junction measurement
temperature abnormal
The cold
junction
is normal
Bit5:Remain
-
-
Bit6:Remain
-
-
Bit7~Bit15:Remain
-
-
Broken even error status word
(
3613
)
Bit status
ON(1)
OFF(0)
Bit0 ~ Bit15 broken
couple detection
When the thermocouple of channel 1 ~
16 is broken, the flag bit is 1
No
channel
break
fault
7. Common problems and solutions
When the module does not work properly, please check in turn:
(1) the connection of the power line and the condition of the relevant
switches and protection appliances, so as to ensure the reliable power
supply of the module;
(2) whether the wiring of user terminals is firm;
(3) check whether the 24Vdc power supply is overloaded.
(4) check the application to ensure that the correct operation method
and parameter range are selected in the application. Special attention
should be paid to the BFM area with special operation timing.
If you still cannot work after the above check, please refer to the
following table.
Phenomenon
Possible Causes
Countermeasures
POWER and
other LED are
off
Loss of power supply or low
voltage
Check the power status and
eliminate
Power switch off or fuse
blown
Check the condition of the
switch, wire or fuse and
eliminate it
Abnormal power wiring
Power supply is damaged
Check and confirm: whether
the voltage between 24V +
and 24V- terminals is within
the normal range
POWER LED
flashes
intermittently
Unstable power supply
Module damaged
RUN LED is off
or on
Module shutdown or crash
Replace the module
RUN LED
flashes slowly
Possible system error
Please check the 3612, 3613
Broken couple error
The output
cannot be
turned off
(OFF)
External wiring contact
short circuit
Check connection and
troubleshoot
The output transistor is
damaged
Replace the module
The output
status indicator
is inconsistent
with the actual
output status
The output transistor is
aging or damaged, or the
indicator is damaged
The serial port
cannot
communicate
normally
The cable connection is
poor, or the signal
properties of the connection
line are wrong, such as A0
and B0 are reversed
Connect the positive and
negative signal lines correctly
Inconsistent setting of
communication
master-slave
characteristics, such as
baud rate, parity, data bits,
address
Set the communication
parameters to be consistent
The communication protocol of
the master and slave is
inconsistent, set the
communication protocol to be
consistent
1
.
Warranty scope refers to the programmable controller body.
2
.
The warranty period is 18 months
, during the warranty period of
normal use, the product failure or damage, our company free
maintenance.
3
.
T
he warranty period starts from the date of production
. The
machine code is the only basis to judge the warranty period. The
equipment without machine code shall be treated as overinsured.
4. Even within the warranty period, a certain maintenance fee will be
charged if:
(1)Failure to operate according to the user's manual;
(2)Machine damage caused by fire, flood, abnormal voltage, etc.
(3)Damage caused when a programmable controller is used for
unusual functions.
(4)Self-disassembly programmable controller
5. The service fee shall be calculated according to the actual cost. If
there is another contract, the contract shall take precedence.
6.If you have any problem, you can contact the agent or contact us
directly.