background image

2

Communication
terminal(6PIN)

Top

16~26AWG

10~15mm

In-line
installa
tion

For security (to prevent electric shock and fire accident), and reduce
the noise, the module of grounding terminal shall be in strict
accordance with the national electrical code requirements, grounding
resistance should be less than 100

Ω

. When more than one module

is grounded, single point grounding should be adopted. The ground
wire cannot form a circuit. As shown in the following figure

4. Terminal Introduction

4.1User terminal

MTCW-12-NT terminal silk screen

User terminal definition table

Remark

Description

24V+,24V-

Input power DC 24V
Ground

A0,B0

RS485(COM0)

T1+~T16+

Channels 1 to 16 are positive for thermocouple
signal input

T1-~T16-

Channels 1 to 16 are negative for thermocouple
signal input

CJ+,CJ-

The external cold junction compensation is
positive and negative. (Note)

Y01~Y08,COM0 Switch output port channel 1~8
Y09~Y16,COM1 Switch output port channel 9~16

Note

CJ+ and CJ- are external thermocouple cold end compensation

terminals (optional), connected with PT100 thermal resistance. When the
connection is not connected or the measured value exceeds the range of
-20

~ 80

, it is automatically switched to the internal cold end

compensation.

4.2 User connection mode

5 things to pay attention to when wiring:

1

All the input and output signal connections and communication

cables shall be shielded layer cables.

2

The thermocouple signal uses the compensation line, the dividing

number should be consistent, positive and negative to

correspond.

3

The signal cable should be away from other cables that may cause

electromagnetic interference, such as the unavoidable set of

metal pipe or wire slot.

4

The metal case of thermocouple should be grounded reliably.

5

The thermostat grounding PGND should be good grounding.

5. Electrical indicator

5.1 Power indicator

Item

Unit

Min

value

Typical

value

Max

value

Remark

Input voltage

range

Vdc

20

24

30

Normal start-up and

working range

Input current

A

/

0.08

/

Normal temperature

rated full load

5.2 Performance indicators

Item

Indicator

Input
signal

Thermocoup
le type

K、J、E、N、T、R、S、B

Input
method

Transistor
output with
open gate

Power supply voltage circuit: 5V ~ 24V; The
maximum circuit power supply voltage circuit:
30V; Loop current: 0.3A /24Vdc; Leakage current
when open:<0.1mA/30Vdc;Minimum load:5mA
(5Vdc~24Vdc)

Control
cycle

Fast

1~100,the unit is 0.1s.The specific value is
determined by the characteristics of the
temperature controlled object

Slow

1~100,the unit is 1s.The specific value is
determined by the characteristics of the
temperature controlled object

Control method

ON/OFF,Hand,PID

Rated

Type K

-100℃~1200℃(-148℉~2192℉)

Reviews: