M
AVTMPFL22M Rev 1 April 2011
26
Pulse Echo (Time Domain Reflectometer, TDR) : Low Voltage Prelocation
The PFL22M1500 has an integrated T.D.R.
1.
Set the rotary Voltage Control Knob (item 21) to the “Zero Start” position
(item 9).
NOTE:
Range and function switch cannot be moved if a mode is active.
2.
Ensure that the Voltage Range switch (item 20) is fully depressed. As we are
using TDR (low voltage prelocation) no HV voltage is required. At this stage
the Status Bar (item 1) will glow “Red”
3.
Set the Mode (Filter) selector switch (item 20) to the TDR and Arc
Reflection group. Both lamps will illuminate, advising that either of these
modes are available.
4.
Depress the pushbutton of the desired mode, in this case TDR. Selection is
confirmed by the pushbutton remaining illuminated and the other
pushbutton extinguishing.
5.
For instructions on the use of the TDR refer to Addendum ***
MTDR100 User Guide
6.
To deselect, and terminate operation depress the TDR pushbutton (item 16),
which also engages the internal earthing/grounding.
7.
The Status Bar (item 1) will glow “Green”.
Arc Reflection : High Voltage Prelocation
Also Arc Reflection Plus (ARP) and Differential Arc Reflection (DART)
1.
Set the rotary Voltage Control Knob (item 21) to the “Zero Start” position
(item 9).
NOTE:: Range and function switch cannot be moved if a mode is active.
2.
Set the Voltage Range switch (item 20) to the desired “surge” range either 8
or 16kV. At this stage the Status Bar (item 1) will glow “Red”.
3.
Set the Mode (Filter) selector switch (item 19) to the TDR and Arc
Reflection group. Both lamps will illuminate, advising that either of these
modes are available.
Summary of Contents for PFL22M1500 Series
Page 2: ......
Page 16: ...M AVTMPFL22M Rev 1 April 2011 6 M...
Page 28: ...M AVTMPFL22M Rev 1 April 2011 18 M...
Page 40: ...M AVTMPFL22M Rev 1 April 2011 30 M...
Page 43: ...AVTMPFL22M Rev 1 April 2011 33 Addendum 1 MTDR100 User Guide...
Page 44: ...M AVTMPFL22M Rev 1 April 2011 34 M...
Page 61: ...AVTMPFL22M Rev 1 April 2011 51 Addendum 2 PFL22M1500INV XX PFL22M1500INV Inverter Option only...
Page 62: ...M AVTMPFL22M Rev 1 April 2011 52 M...
Page 68: ...M AVTMPFL22M Rev 1 April 2011 58 M...
Page 69: ...AVTMPFL22M Rev 1 April 2011 59 Addendum 3 Cable Fault Location Applications Guide...
Page 70: ...M AVTMPFL22M Rev 1 April 2011 60...
Page 77: ...AVTMPFL22M Rev 1 April 2011 67 Megger Quality System Certificate...