UK
Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342
UNITED STATES
4271 Bronze Way
Dallas TX 75237-1019 USA
T 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
OTHER TECHNICAL SALES OFFICES
Valley Forge USA, College Station USA,
Sydney AUSTRALIA, Danderyd SWEDEN,
Ontario CANADA, Trappes FRANCE,
Oberursel GERMANY, Aargau SWITZERLAND,
Kingdom of BAHRAIN, Mumbai INDIA,
Johannesburg SOUTH AFRICA, Chonburi THAILAND
CERTIFICATION ISO
Registered to ISO 9001:2000 Cert. no. Q 09290
MIT200_DS_en_V08
www.megger.com
Megger is a registered trademark
3
Terminal characteristics
ORDERING INFORMATION
Description
Order Code
250 V/500 V Insulation and continuity tester
MIT220-EN
250 V/500 V/1000 V Insulation and continuity tester MIT230-EN
Included accessories
Test lead set and crocodile clips
1002-001
Carry case
5410-419
Optional accessories
Test lead set and crocodile clips
1002-001
Fused test lead set (1 pair)
1002-015
Removable protective holster
5410-346
Carry pouch
6220-773
SPECIFICATIONS
Insulation range
Nominal test voltage:
1000 V, 500 V, 250 V (d.c.)
Measurement range
10 kΩ - 1000 MΩ on all ranges
Terminal voltage on open circuit (d.c.):
-0 % +25 % of rated voltage
Short circuit current:
205 mA +10 mA -5 mA
>18 mA (10 - 100 Ω)
Test current on load:
>1 mA at minimum pass values of insulation as specified in
BS 7671, HD 384, IEC 364 and VDE 0413 part 1
Chart/graphic
Continuity range
Measuring range:
0,01 Ω - 100,0 Ω
(0 -50 Ω on analogue scale)
Open circuit voltage: 5 V ±1 V
Accuracy (at 20° C)
MIT220, 230:
±0,01 Ω to 9,99 Ω ± 3 % ±2 digits
10,0 Ω to 99,9 Ω ± 5 % ±2 digits
Zero offset adjust:
MIT220, 230:
0 to 9,99 Ω
Continuity buzzer
MIT220, 230:
Operates at < 2 Ω
Default voltmeter
MIT220,230:
>25 V a.c. or d.c. is applied display will operate as a voltmeter.
Range:
25 V to 600 V @ 50/60 Hz & d.c.
Accuracy:
25 V to 450 V a.c./d.c. ± 1% ± 1 digit
450 V to 600 V a.c. ± 2% ± 1 digit
Test inhibit
If more than 50 V is detected, testing
will be inhibited.
Auto power down
Auto power down operates after
10 minutes if left in standby mode.
Operating temperature
range and humidity
-10 °C to +55 °C
93 % R.H. at +40 °C max.
Storage temperature range
and humidity
-25 °C to +65 °C
IP rating
IP40
Fuse
500 mA (F) 600 V, 32 x 6 mm
Ceramic HBC 50 kA minimum.
Display shows if fuse is ruptured.
Over-voltage safety
category
Meets the requirements of IEC61010-
1 Cat III 600 V phase to earth.
Automatic discharge
After an insulation test the item
under test will be discharged
automatically. Any voltage present
will be indicated on the display so
that the discharge can be monitored.
Power supply
Battery 6 x 1,5 V cells IEC LR6 type
(AA alkaline).
Rechargeable NiMH cells may be
used.
Battery condition is constantly shown
on the display as a four section bar-
graph.
Battery life
3000 consecutive tests (5 seconds per
test) on any test using 2 Ah batteries.
Weight
All units: 530 gms ± 5 %
Dimensions
All units: 195 x 98 x 40 mm
EMC
In accordance with IEC61326-1