background image

UK

Archcliffe Road Dover

CT17 9EN England

T +44 (0) 1304 502101

F +44 (0) 1304 207342

[email protected]

UNITED STATES

4271 Bronze Way

Dallas TX 75237-1019 USA

T 800 723 2861 (USA only)

T +1 214 333 3201

F +1 214 331 7399

[email protected]

OTHER TECHNICAL SALES OFFICES

Valley Forge USA, College Station USA,  

Sydney AUSTRALIA, Danderyd SWEDEN,  

Ontario CANADA, Trappes FRANCE,  

Oberursel GERMANY, Aargau SWITZERLAND, 

Kingdom of BAHRAIN, Mumbai INDIA, 

Johannesburg SOUTH AFRICA, Chonburi THAILAND

CERTIFICATION ISO

Registered to ISO 9001:2000 Cert. no. Q 09290

 

MIT200_DS_en_V08

www.megger.com

Megger is a registered trademark

3

Terminal characteristics

ORDERING INFORMATION

Description 

Order Code

250 V/500 V Insulation and continuity tester 

MIT220-EN

250 V/500 V/1000 V Insulation and continuity tester MIT230-EN

Included accessories

Test lead set and crocodile clips 

1002-001

Carry case 

5410-419

Optional accessories

Test lead set and crocodile clips 

1002-001

Fused test lead set (1 pair) 

1002-015

Removable protective holster 

5410-346

Carry pouch 

6220-773

SPECIFICATIONS

 

Insulation range

Nominal test voltage:
1000 V, 500 V, 250 V (d.c.)

Measurement range

10 kΩ - 1000 MΩ on all ranges

Terminal voltage on open circuit (d.c.):
-0 % +25 % of rated voltage

Short circuit current:
205 mA +10 mA -5 mA
>18 mA (10 - 100 Ω)

Test current on load:
>1 mA at minimum pass values of insulation as specified in
BS 7671, HD 384, IEC 364 and VDE 0413 part 1

Chart/graphic

 

Continuity range

Measuring range:
0,01 Ω - 100,0 Ω
(0 -50 Ω on analogue scale)

Open circuit voltage: 5 V ±1 V

Accuracy (at 20° C)
MIT220, 230:
±0,01 Ω to 9,99 Ω ± 3 % ±2 digits
10,0 Ω to 99,9 Ω ± 5 % ±2 digits

Zero offset adjust:
MIT220, 230:
0 to 9,99 Ω

Continuity buzzer

MIT220, 230:
Operates at < 2 Ω

Default voltmeter

MIT220,230:
>25 V a.c. or d.c. is applied display will operate as a voltmeter.

Range:
25 V to 600 V @ 50/60 Hz & d.c.

Accuracy:
25 V to 450 V a.c./d.c. ± 1% ± 1 digit
450 V to 600 V a.c. ± 2% ± 1 digit

Test inhibit

If more than 50 V is detected, testing 
will be inhibited.

Auto power down

Auto power down operates after  
10 minutes if left in standby mode.

Operating temperature 
range and humidity

-10 °C to +55 °C
93 % R.H. at +40 °C max.

Storage temperature range 
and humidity

-25 °C to +65 °C

IP rating

IP40

Fuse

500 mA (F) 600 V, 32 x 6 mm 
Ceramic HBC 50 kA minimum.
Display shows if fuse is ruptured.

Over-voltage safety 
category

Meets the requirements of IEC61010-
1 Cat III 600 V phase to earth.

Automatic discharge

After an insulation test the item 
under test will be discharged 
automatically. Any voltage present 
will be indicated on the display so 
that the discharge can be monitored.

Power supply

Battery 6 x 1,5 V cells IEC LR6 type 
(AA alkaline).
Rechargeable NiMH cells may be 
used.
Battery condition is constantly shown 
on the display as a four section bar-
graph.

Battery life

3000 consecutive tests (5 seconds per 
test) on any test using 2 Ah batteries.

Weight

All units:  530 gms ± 5 %

Dimensions

All units: 195 x 98 x 40 mm  

EMC

In accordance with IEC61326-1