www.megger.com
38
General Information
Current (via Clamp meter):
Intrinsic accuracy:
±5.0% ±3 digits
Resolution:
0.1 mA
EN61557 Range:
0.5 mA – 199 A
Max service error:
±10% ±2 digits
mV Sensor input
Including temperature (third party module)
±1.0% ±2 digits
Range
0.0 mV to ±199.9 mV dc
Resolution
0.1 mV
Internal memory
Capacity
1000 results
Bluetooth
®
communication
Power consumption:
Nominal minimum:
60 mA (Voltage range with no input voltage)
Nominal maximum:
350 mA (Active Insulation test set to 1000 V / 1 MΩ)
Range:
-20 °C to +55 °C
Temperature (via 3rd Party Module):
Intrinsic accuracy:
±1.0% ±2 digits
Resolution:
1 °C
Range:
-20 °C to +100 °C
Environmental Specification.
Temperature
Operational range:
-10 °C to +55 °C
Storage range:
-25 °C to +70 °C
Humidity
Operating humidity:
90% R.H. at +40 °C max.
Altitude
2000 m to full safety specification.
Weight:
1000 g ±10% including batteries but excluding test leads, accessories and carry case.
Dimensions:
150 mm high x 85 mm wide x 235 mm deep, (6 in. x 3.5 in. x 9.5 in.)
IP rating:
IP54
Power Supply.
Battery:
Primary, 6 x 1,5 V cells IEC LR6 type (AA alkaline,).
Battery: Rechargeable:
6 x 1.2 VNiMH cells EC HR6.
Display shows rechargeable [NiMH] when the battery type is changed in “Setup options” on page 26.
Safety / EMC.
EMC In accordance with IEC61326 edition 2.
Locations: Class B locations
Safety in accordance with IEC 61010 -1 2010 + 61010 -30:2010
Installation Category: 600 V CAT III / 300 V CAT IV. (Max Phase to Phase 550 V)
In addition switch probe and test leads are designed to meet IEC 1010-031:2008, Double insulated to
Installation Category III, 300 V phase to Ground, 500 V phase to phase.