8.16 Useful information
It is only necessary to test the 10mA and 30mA at 1/2xI, 1xI and 5xI. All other RCDs only need to be tested at 1/2xI and 1xI.
Always press the RCD TEST button on the RCD to ensure the function works.
It is recommended the RCD test button is tested AFTER the timing tests above are complete. This can identify RCDs that may stick or fail
if not checked periodically.