Megger IDAX 300 User Manual Download Page 23

AG033586EE

ZP-AG03E

IDAX 300/322/350

23

4 IDAX 5 SOFTWARE  

4.2. Measurement using 
Individual Temperature 
Correction for single 
material (ITC1)

This type of measurement is mainly intended 
for bushing and current transformer condition 
assessment. 

Start the IDAX 5 software

1] 

Press “New File” button to set-up the 
measurement.

2] 

Press “Single Test” tab and then “ITC1” 
button.

3] 

Select suitable “Test Object” template, e.g. 
“Bushings” (transformer bushing).

4] 

Enter mandatory temperature data 
for ambient and object temperature 
(highlighted). Object temperature (°C) refers 
to insulation temperature. Top oil or winding 
temperature is normally used as insulation 
temperature for the transformer.

Note

  IDAX 5 software estimates bushing tempera-

ture as average between ambient and object 
temperature.

5] 

Select appropriate “Insulation Type” for 
given bushing from dropdown menu.

6] 

Press the green “Create” button.

7] 

Select the folder where the measurement 
will be saved and name the file.  
The default name is composed of: “Location” 
+ ”Designation” + ”Date + Time”.

Now you have a “File” with one “Test”, the C1 
configuration by default, visible on the legend in 
the left-hand side of the main window (see picture 
below). On the top you have several “Tabs” showing 
Nameplate, the Test (Named ITC1), Hook-up, Graph 
(and table) and Settings.

8] 

Press the “Hook-up” tab to show the cable 
connections from the instrument to the 
object.

There are two pictures showing the two versions of 
IDAX 300, IDAX 300 delivered 2011 or earlier (to the 
left) and IDAX 300 delivered 2012 or later.

Note

  If you have an older IDAX 300 with two input 

connectors for each channel, the SENSE input 
must NOT be connected.

9] 

Ensure that the safety ground cable is 
connected to the IDAX 300 instrument and 
to the station ground near the test object/
transformer. This cable acts as safety ground 
AND test input lead.

10] 

Make sure that all HV phase terminals and 
any exposed neutral terminal are connected 
together. While connecting together the 
terminals with bare copper wire, the phases/
windings should be connected to ground.

11] 

Make sure that all LV phase terminals and 
any exposed neutral terminal are connected 
together. While connecting together the 
terminals with bare copper wire, the phases/ 
windings should be connected to ground.

12] 

Connect the Generator cable to the high 
voltage winding – according to the picture in 
Hookup tab.

13] 

Connect the Red input lead to the test pin 
of the bushing – according to the picture in 
Hook-up tab.

14] 

Remove any grounding connection from the 
windings before you start the measurement.

15] 

Press the “Connect” button located on the 
right-hand side of the main window or press 
the “Start” button. This will connect to IDAX  
300 if not connected yet.

16] 

Press “Start” to initiate the measurement/test

Measurement

The measurement will start a routine initiation 
procedure where the system measures all 
capacitances, including stray capacitances in the 
test object as well as the interference level. This 
routine procedure sets up the instrument and the 
model ensures the highest possible accuracy over the 
selected frequency range.

Analysis

During the ITC1 test an automatic correction is 
performed from the first point and results are 
presented in the “Analysis results” section. The 
analysis is complete when %DF values are presented 
at all three frequencies.

Insulation assessment guidelines

The default limits of %DF at 20°C are based on 
recommendations given in CIGRE TB 445, which gives 
values for new and aged bushings at 50/60 Hz and 
15 Hz. The materials covered are Resin Impregnated 
Paper (RIP), Oil Impregnated Paper (OIP) and Resin 

Summary of Contents for IDAX 300

Page 1: ...User guide Art No ZP AG03E Doc AG033586EE V06a 2020 IDAX 300 322 350 IDAX 5 Software Insulation diagnostic analyzers...

Page 2: ......

Page 3: ...atics and technical descriptions or software listings that disclose source code are for informational purposes only Reproduction in whole or in part to create working hardware or software for other th...

Page 4: ...es 17 Connection examples Power transformers 17 4 IDAX 5 Software 20 4 1 Moisture test 20 Start the IDAX 5 software 20 Measurement 21 Disconnect re connect 22 4 2 Measurement using Individual Tempera...

Page 5: ...AG033586EE ZP AG03E IDAX 300 322 350 5...

Page 6: ...or reliable test results in high interference environments The software makes testing both easier and faster allowing transformer moisture and oil assessment in about 23 minutes 20 C IDAX measures the...

Page 7: ...e factory for repair must be shipped prepaid and insured Contact your Megger representative for instructions and a return authorization RA number Please indicate all pertinent information including pr...

Page 8: ...d These notices appear in the format shown below and are defined as follows Warning Warning as used in this manual is defined as a condition or practice which could result in personal injury or loss o...

Page 9: ...properly grounded both through its AC power cord and through the ground connector The AC power cord is the disconnecting device 8 Always disconnect test leads from test specimen before attempting to d...

Page 10: ...the test set can be maintained by occasional cleaning of the case panel and cable assemblies The outside of the carrying case can be cleaned with detergent and water Dry with a clean dry cloth The co...

Page 11: ...AG033586EE ZP AG03E IDAX 300 322 350 11 2 Safety...

Page 12: ...and Input 2 blue First and second input channel Do not connect to mains or energized test objects Do not connect directly to Generator output 8 TEST Test inputs Can be used for controlling basic func...

Page 13: ...ction to test object ground This is also used as measurement input Always connect the instrument to station earth ground using the separate earth ground cable The separate earth ground wire should be...

Page 14: ...ound connector Connector for connection to test object ground This is also used as measurement input Always connect the instrument to station earth ground using the separate earth ground cable The sep...

Page 15: ...the unit using the on off mains switch and disconnecting the mains cord IDAX 350 can be used as a central computer controlling other test instruments e g Megger FRAX and TTR Megger software is checke...

Page 16: ...The IDAX unit will be detected by the IDAX software and the address identified Allow connection to the IDAX instrument Note If you have several instrument connected via e g a company network confirm a...

Page 17: ...ing to change cable connections on the transformer The extended versions IDAX 300S and IDAX 350 as well as IDAX 322 have dual separate current measurement channels that allows for two completely indep...

Page 18: ...a three winding transformer the IDAX 300 second input channel is utilized The test leads need to be moved between test 2 and test 3 and between test 4 and test 5 If using IDAX 300S 322 or IDAX 350 wit...

Page 19: ...AG033586EE ZP AG03E IDAX 300 322 350 19 3 Instrument description...

Page 20: ...former 4 Enter mandatory temperature data for ambient and object temperature highlighted Object temp C refers to insulation temperature Top oil or winding temperature is normally used as insulation te...

Page 21: ...ccording to the picture in Hook up tab 13 Remove any grounding connection from the windings before you start the measurement 14 Connect to the IDAX instrument using the Connect button located on the r...

Page 22: ...Recommendations in IEC 60422 and IEEE C57 106 Assessment of liquid conductivity is also based on experience as well as on IEC 60422 and IEEE C57 106 due to lack of more specific standards The limits f...

Page 23: ...he IDAX 300 instrument and to the station ground near the test object transformer This cable acts as safety ground AND test input lead 10 Make sure that all HV phase terminals and any exposed neutral...

Page 24: ...loaded to the IDAX 5 when it is re connected 4 3 Operating IDAX 5 Left section of the main window When no file is loaded the left section shows the latest used files for quick access and a button for...

Page 25: ...ght closes the file At the bottom there is a button for deleting the selected sweep as well as the button for opening a new file Middle section of the main window Nameplate tab The Nameplate Tab shows...

Page 26: ...s for capacitance dissipation factor tan delta and excitation current can be measured Multiple recordings can be made by repeating start Results are presented in table format DC In the DC tab you can...

Page 27: ...two internal voltage sources One of maximum 200 V peak approximately 140 V RMS output voltage The second source has maximum 10 Vpeak approximately 7 V RMS By selecting External VAX and connecting the...

Page 28: ...alysis are available based on single or two materials Single material Single material analysis is invoked when measuring bushings current transformers and other rather homogeneous materials 1 Press Ed...

Page 29: ...t materials will let you choose which materials to use in the analysis window for specific objects A transformer usually has cellulose while an instrument transformer typically has Kraft paper as insu...

Page 30: ...2 0 program in IDAX 4 1 Export Opens up a dialog box to export measurement data into text format compatible with e g MODS 2 0 Report Opens a dialog where selection between HTML PDF and MS Word report...

Page 31: ...Change test voltage level by changing test voltage Change temperature of object insulation tested Start Stop Remake 1 Press button Start to start a test and press the button Stop to stop a test If yo...

Page 32: ...asurement with automatic estimation of moisture content Besides qualitative analysis of moisture content parameters such as capacitance dissipation factor both measured and calculated at 20 C accordin...

Page 33: ...AG033586EE ZP AG03E IDAX 300 322 350 33 4 IDAX 5 Software...

Page 34: ...Cat No AG 90010 The second option means that the IDAX instrument is available since it does not need to be sent away for calibration The calibration procedure is easy to perform using the optional Ca...

Page 35: ...AG033586EE ZP AG03E IDAX 300 322 350 35 5 Calibration...

Page 36: ...s Lower the InitFrequency in the measurement plan see also Measurement variables Lower the test voltage 4 If you try to use an old version of IDAX software version 3 2 or earlier but the firmware in I...

Page 37: ...ectrode and guard e g measuring a UST configuration between high and low voltage windings of a two winding transform er the low voltage winding has too low impedance to ground inductive voltage transf...

Page 38: ...red by applying a voltage across the sample This voltage will generate a current through the sample By accurately measuring the voltage and the current the impedance can be calculated see illustration...

Page 39: ...indings as one simple capacitance is a simplification of the real conditions This is one of the reasons why the modelled geometry may not correspond exactly to the real geometry in the transformer In...

Page 40: ...f is frequency Another model more often used in insulation diagnostics is the complex capacitance model describing the insulation impedance as a complex capacitance where the imaginary part of the cap...

Page 41: ...ither a dielectric model or a conductive model In the dielectric model the material capacitance the permittivity is a complex function describing both the capacitance and the loss Whereas in the condu...

Page 42: ...higher Accuracy 0 5 0 0001 45 70 Hz C 100 pF with VAX 020 and IDAX 322 0 5 0 0002 45 70 Hz C 300 pF 1 0 0003 1 mHz 100 Hz C 1000pF 2 0 0005 100 Hz 1 kHz C 1000 pF Max AC interference 1mA 1 10 SNR IDA...

Page 43: ...AG033586EE ZP AG03E IDAX 300 322 350 43...

Page 44: ...nstallation 15 Installation of IDAX 5 software 15 Instrument safety 8 ITC1 23 M Maintenance 9 Measurement technique 38 Modelling principles 39 Moisture test 20 O Operating IDAX 5 24 P Preparing instru...

Page 45: ...AG033586EE ZP AG03E IDAX 300 322 350 45 8 Specifications...

Page 46: ...nt Low Resistance Ohmmeters Motor Phase Rotation Test Equipment Multimeters Oil Test Equipment Portable Appliance Tool Testers Power Quality Instruments Recloser Test Equipment Relay Test Equipment T1...

Reviews: