4 IDAX 5 SOFTWARE
4.1 Moisture test
This section describes the procedure to perform
moisture assessment measurements on a 2-winding
(single or three-phase) power transformer using IDAX
5 software. Step-by-step instructions are provided,
intended for the non-experienced user.
Start the IDAX 5 software
1]
Begin set-up measurement by pressing the
“New File”-button.
2]
Select “Single Test” tab, “Moisture” button
(see left-hand side arrows).
3]
Then choose suitable test object template,
e.g. 2W-transformer (two-winding
transformer).
4]
Enter mandatory temperature data
for ambient and object temperature
(highlighted).
Object temp. (°C) refers to insulation
temperature. Top oil or winding temperature
is normally used as insulation temperature
for the transformer. Designation is the
tag or identification code of the UUT
(unit under test) e.g. T2 (transformer
No. 2). Suggested file name will be
“Lo”Desig”Date”+Time”.
5]
Press the green “Create”-button at the low
right-hand side of the window.
6]
Select the folder where the measurement
will be saved and name the file.
The default name is composed of:
“Lo”Desig”Date”+Time”.
Note
At any time you may access Nameplate and
change/add information by pressing “Edit
Nameplate” button in the program main
window.
4
I
DAX 5 Software
Summary of Contents for IDAX 300
Page 2: ......
Page 5: ...AG033586EE ZP AG03E IDAX 300 322 350 5...
Page 11: ...AG033586EE ZP AG03E IDAX 300 322 350 11 2 Safety...
Page 19: ...AG033586EE ZP AG03E IDAX 300 322 350 19 3 Instrument description...
Page 33: ...AG033586EE ZP AG03E IDAX 300 322 350 33 4 IDAX 5 Software...
Page 35: ...AG033586EE ZP AG03E IDAX 300 322 350 35 5 Calibration...
Page 43: ...AG033586EE ZP AG03E IDAX 300 322 350 43...
Page 45: ...AG033586EE ZP AG03E IDAX 300 322 350 45 8 Specifications...