background image

GENERAL DESCRIPTION

The  Megger BMM2000 Series instruments are battery
powered Insulation and Continuity testers, with a measurement
capability from 0,01

Continuity to 200G

Insulation. 

Offering multi-voltage facilities, the instruments take full
advantage of microprocessor technology and feature a large
liquid crystal display combining digital and analogue readings.
The analogue display has the benefit of indicating trends and
fluctuations in readings, while the digital readout gives direct
accurate results. The display is also backlit giving clear visibility
even in low light conditions.

The BMM2000 Series instruments have the unique capability of
being able to measure voltages down to a resolution of 0,1mV.
This gives the user the option to fit a wide variety of
transducers to further enhance the capabilities of the BMM
Series instruments, eg temperature or humidity measurement.

A customised connector on the top of the instrument enables
the optional Megger SP1 Switched Probe to be used for two
handed probe operation.

The 250V, 500V and 1000V ranges can be used to test
electrical installations in compliance with BS7671 (16th Edition
IEE Wiring Regulations) IEC364 and HD384, since each range
has a 1mA minimum test current at the minimum pass values
of insulation specified in these documents. The 100V range is
ideal for testing telecommunications equipment which would be
damaged by higher voltages. The 50V range is useful for
testing sensitive equipment, such as electronic components,
and computer peripherals.

The BMM2000 series instruments have a current facility which
enables up to 500mA to be measured, (not ESD models), this
together with 

, V and mV ranges means that the instrument can

realistically be used in situations where previously a multimeter
would be needed.For higher currents an optional current clamp is
available.

Designed to IEC1010-1 the BMM2000 Series are protected
against connection to a 500V Category III supply. The
instruments have a basic accuracy of ±2% at 20°C. The
instruments are waterproof and dustproof to IP54. This helps
maintain accuracy and ensures maximum reliability in harsh
environments.

OPERATION

Refer to Safety Warnings before using the instrument 

Testing is automatically inhibited if:

An external voltage >25V is present when switched to any
insulation range position. 

An external voltage >10V is present on all other ranges
(excluding OFF/V).

The external voltage is indicated on the display, on insulation
ranges an audible bleeper will sound if a test is attempted.

Summary of Contents for BMM2000 Series

Page 1: ...ave no broken or cracked insulation Ensure that hands remain behind guards of probes clips when testing U K Safety Authorities recommend the use of fused test leads when measuring voltage on high ener...

Page 2: ...Regulations IEC364 and HD384 since each range has a 1mA minimum test current at the minimum pass values of insulation specified in these documents The 100V range is ideal for testing telecommunication...

Page 3: ...is activated by pressing the key The backlight will remain illuminated for approx one minute before automatically switching off to conserve battery life alternatively the key can be re pressed Insula...

Page 4: ...paid to the terminals Also attempt to reduce any leakage that may give erroneous results on the item under test Polarisation Index Testing Polarisation Index PI is the term applied to the Dielectric A...

Page 5: ...ation is retained in non volatile memory and so will be remembered when the instrument is switched off 1 Select the Continuity range 2 Short the test leads across a known good conductor using prods 3...

Page 6: ...ent The diode symbol will appear if the voltage developed across the terminals is within semi conductor junction limits These features together with the small test current and wide measurement range 0...

Page 7: ...icate the zero has been adjusted 1 Select the uF range 2 Disconnect the test leads from the circuit under test 3 When the reading has stabilised press the TEST button The zero offset symbol will appea...

Page 8: ...he user should the probe be used accidentally in conjunction with a test lead in the low terminal Relates to transient overvoltage likely to be found in fixed installation wiring Do not use the probe...

Page 9: ...digits 0 8 per G 100V 20G 2 2 digits 2 0 per G 50V 10G 2 2 digits 4 0 per G Accuracy BMM2000 Range Full Scale Accuracy 1000V 20G 2 2digits 0 2 per G 500V 10G 2 2 digits 0 4 per G 250V 5G 2 2 digits 0...

Page 10: ...460 Hz 5 7 digits 10mV to 1999mV a c 16 460 Hz 5 5 digits d c milliVolts zeroing Up to 9 9mV Input resistance 3M Capacitance BMM2080 Measuring Range 0 1nF to 9 99uF Accuracy 3 2 digits 0 2nF uF zeroin...

Page 11: ...imit Min Indicated Limit Min Indicated Reading Reading 0 10 0 14 2 00 2 12 0 20 0 25 3 00 3 16 0 30 0 35 4 00 4 20 0 40 0 46 5 00 5 24 0 50 0 56 10 00 10 8 0 60 0 66 20 00 21 2 0 70 0 77 30 00 31 6 0...