5 OPERATING INSTRUCTIONS
5.2 Measurement with
max. charge, I=I MAX
1]
Read the section 5.1 General instructions.
2]
If applicable, connect the ground cable (pro-
tective earth).
3]
Make the desired settings in the
SET
options.
In this example
LOG
and
P / F
are disabled (set
to OFF).
4]
Attach the test cables.
5]
Turn the function selector to desired
I = I max
position.
The instrument indicates that it is charging
the capacitor by a repeated sound and on
the display shows alternating "CAP" and
"CHG" and the lock symbol.
Charging
6]
The MOM2 is ready for a measurement when
the lock symbol disappears.
Ready for test
7]
Press the
TEST
button on MOM2 or the pull
the trigger on the probe.
A continuous audio signal tells that the
measurement is in progress.
Two short signals tells that the measurement
is complete.
8]
The result is shown on the display, see figures
below.
Over the resistance value "100 μΩ" toggles
the maximal and minimal current values dur-
ing the test. "268 A" and "250 A"
Pictures shows the two display views..