BD0333JE
ZP-BD03E
MOM2
17
4 FUNCTIONS AND SET UP
4.5 Minimum current – I
min
SET / I min
Display abbreviations
SEL
Select
Set-up
1]
Select
SET / I min
. Present setting is displayed.
2]
Press and hold OK key until digits start to
blink under the "SEL" letters.
3]
Select value, 50 or 100, using the
▲ ▼
keys.
4]
Press OK key to confirm.
To cancel press C key or turn the function
selector to another position.
Result after a measurement
If the chosen value is not reached during a measure-
ment it will result in a notification on the display and
by an audio signal.
Picture shows an example after a measurement. The I min
limit "50 A" has not been achieved, indicated by the "<"
character to the left.
The current measured during the test is shown in the upper
row. The value shown toggles between the max and min
current during the test. In this case it is the minimum cur-
rent showing "> 037 A".
4.6 Data logger – LOG
The data memory can store totally
104
measurements
and this capacity is shared by the two log modes.
SET / LOG
Display abbreviations / description
SEL
Select
oFF
OFF
1A1
Label for Breaker, Phase, Interrupter
1234
Running numbers
LOG modes
OFF
When the log is OFF only the latest value is stored and only
until the performance of a following measurement, which
overwrites the previous one.
Circuit breaker testing mode,1A1
This mode is primarily designed for measurement on circuit
breakers. The three characters (1A1) are supposed to indi-
cate: Breaker, Phase, Interrupter.
Measurement is automatically stored, provided that
there are less than three measurements stored on the
selected object label. Each label can store three meas-
urements. See also section 5.6 Measurement using
the log function.
Running numbers mode, 1234
The measurements are numbered in numerical order (1 to
1999)
Measurement is automatically stored, provided that
the memory is not full.