Maintenance notes
We advise you to keep the equipment clean and to ensure the installation is in a dry and ventilated area.
Checking that components are connected and their signal strength in
Diagnostic Mode
To activate the diagnostic mode, press the transparent lens between the sounder and the callpoint on the
master unit for 5 seconds.
The diagnostic mode is activated when the green LED of the master unit blinks.
Each connected unit beeps, the beeps correspond to the quality of the signal strength.
To end the diagnostic mode just press the transparent lens once.
Faults
Master unit Faults
A fault is identified by a flashing orange light on the master unit and a number of beeps on the master and/or the MCP.
Number of beeps Faulty Unit
Fault
Explanation
1 Master
Battery
The master unit battery is faulty
2 Master MCP
Battery
The master unit MCP battery is faulty
3 MCP
Battery
An MCP has a faulty battery
4 MCP
Communication
An MCP has a communication fault
Manual call point (MCP) faults
Number of beeps Faulty Unit
Fault
Explanation
1 MCP
Battery
The manual call point battery is faulty
2 MCP
Communication
No signal has been recieved from the
Battery Fault
Replace the defective Lithium 3Vcc CR 17 345 for the MCP including the One installed in the master unit.
Replace the 9V 6 LR 61 battery inside the master unit.
Communication Fault
Go in to the diagnostic mode described earlier to check the quality and strengh of the signal, relocate if required or
investigate if there is a new obstruction or interference causing the fault.
Clearing Configuration / Decommissioning
If at any point you are unsure of the number of MCP’s paired with the system, or are having problems commissioning,
or wish to relocate the wireless system or reduce the number of paired units, then you will
need to decommission
the slaves one at a time.
Both the Master P300W and D300W can not be decommissioned, however, the D300W
can be moved and re-commissioned, using the normal procedureas set out in the step 3 to a different master
To decommission a slave P300W or a C300W, you will need to:
Press and hold the CONFIG button and the VALID button together until you here 3 short beeps, 4 long beeps and then 1
short beep and then release the buttons, the C300W is now decommissioned from the system and can be added back
using the normal procedure as set out in step 2.