background image

8. Once positioned in its fi nal setting press and release the VALID key on the slave it will beep 3 times very quickly 
to enter normal service.
9. The master will also beep 4 times as it enters normal service. The system is now operational.

Note:

 to add further C300W or stand alone P300W units (as a slave to the master) repeat 

previous steps 1 to 9.

Note: 

maximum extra components as slaves is 9 .

step

  

 

 

 

adding a D300W radio smoke detector

Note:

 Do one confi guration at a time

1. To link the smoke detector to the master, open the master P300W box.
2.  Place the D300W unit you wish to link next to the master unit and remove the battery isolation tag from the 
underside of the smoke detector. Put the key away in the location space provided (see below on the right).

3. Within 20 seconds of removing the tag, press the clear button on the side of the D300Wsmoke detector and the 
unit will beep, release the button and the LED will fl ash Blue.
4. Press the VALID button in the master unit until you hear a long beep and release.
5. The smoke detector is now linked to the master unit and will now enter the

 

‘signal strength’ mode.

6. Take the detector to the required location for installation, the detector will regularly beep up to 5 times to 
    indicate signal strength.

  Number of Beeps 

       1   

       2      

           3 

              4 

                   5

  Signal Strength           Very weak                  Weak 

       Medium                  Good               Very good

7.  If the signal strength is acceptable press the button on the side of the smoke detector and it is now paired 
     with the master. The system is now operational.

Note

: to add further smoke detectors repeat previous steps 1 to 6.

0330 999 2233

www.fi redepot.co.uk

sales@fi redepot.co.uk

5

Summary of Contents for P300W

Page 1: ...setting up your wireless system P300W C300W D300W and wireless interface Standards NFS 61 936 NFS 32001 EN 54 11 0330 999 2233 www firedepot co uk sales firedepot co uk...

Page 2: ...operation autonomy 5 years with at least 5 minutes alarm Installation Method Surface mounted Sounder Integral 90db within 2 meters Strobe Lights Integral high power LEDs Dimensions 126 W x242 H x75 D...

Page 3: ...em requires that you make a P300W unit the master and all other components slaves Further P300W units and or both C300W or D300W stage one opening and closing your master P300W unit Open your P300W un...

Page 4: ...MCP Refer to Step 2 stage one on how to access the MCP step 2 Your C300W unit stage one opening your C300W unit Simply unscrew the holding screw in the front of the box then lift off the front face s...

Page 5: ...Slave unit is either another P300W C300W or D300W 2 Place the slave next to the master unit 3 Press the CONFIG button in the slave unit for 5 seconds the unit will beep to indicate each second and the...

Page 6: ...he location space provided see below on the right 3 Within 20 seconds of removing the tag press the clear button on the side of the D300Wsmoke detector and the unit will beep release the button and th...

Page 7: ...Battery The manual call point battery is faulty 2 MCP Communication No signal has been recieved from the Battery Fault Replace the defective Lithium 3Vcc CR 17 345 for the MCP including the One instal...

Reviews: