00252 

Remote stop buttons

 

AGDS-V 

To EM Stop connections in the 

panel 

Use terminals TB2 A & C 

Use terminals TB2 A & C 

Remote stop buttons can be  connected to the panel terminal 
marked as “EM STOP” (number 6 ).  
 
The remote buttons must be wired as shown in order to provide a 
“closed contact” for the control panel. 

 
If thermal links are to be installed these should be wired 
in series with the EM stop buttons 

To EM Stop connections in the 

panel 

Indicator bar shows when 
pressed 

Normal 

EM-Stop Activated 

    Multiple Stop Buttons 

    Single Stop Buttons 

     Resetting (indicator bar) 

The stop buttons supplied by Medem are of a “Push Glass, key resettable” style, when activated a yellow indicator bar will 
show and the unit will require resetting using the key provided. 

Multiple stop buttons are wired in series. 
 
If thermal links are to be installed these too should 
be wired in series with the EM stop buttons 
 

Use terminal TB2 A & C 

Summary of Contents for AGDS-V

Page 1: ...to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commis...

Page 2: ...Medem UK Ltd such that they only require to be connected to the panel and functionally tested In the event of a high alarm from one of the sensors the system will isolate the gas supply by closing a...

Page 3: ...r detectors Methane LPG CO CO2 Oxygen Temperature 10 Panel Mode switches factory set do not alter 11 Internal tone on off 12 Spare 13 Learn field device button press once only when all detectors are c...

Page 4: ...e commissioned a er installa on by Medem UK This will extend the warranty period from 5 years to 10 years and ensure the system is working as designed Please see warranty condi ons that came with the...

Page 5: ...ctions for more guidance AGDS V Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one another daisy chain Address...

Page 6: ...d between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional informati...

Page 7: ...d be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicato...

Page 8: ...er Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry...

Page 9: ...lay that all the detectors have been recognised by the panel 10 At this point press the reset button the panel will open the gas valve Checklist AGDS V Please do not hesitate to call for advice on the...