00252 

System Settings

 

AGDS-V 

Status 

 

 

 

 

 

AX1 

AX2 

AX3 

AX4 

EM Stop - ES 

OFF 

OFF 

ON 

OFF 

Fire Panel Active -FA 

ON 

OFF 

ON 

OFF 

High Alarm - HA 

OFF 

ON 

ON 

OFF 

Low Alarm - LA 

ON 

ON 

ON 

OFF 

Gas On/Off   

OFF 

OFF 

OFF 

ON 

Detector Fault - DF 

ON 

OFF 

OFF 

ON 

Generic Fault (ES, FA, HA, LA, DF)  

OFF 

ON 

OFF 

ON 

There are two mains rated relays 

4 & 5

, for connection to a BMS or Sounder/Beacon. Each relay is able to be set to 

report one of the status's in the table below.  
Max switching 230 volts 5amp’s 

   4, 5 & 16. BMS Relays and setting switch 

Notes. 

It is recommended that all systems are commissioned a er installa on by Medem UK. This will extend the warranty period from 5 

years to 10 years and ensure the system is working as designed.  

Please see warranty condi ons that came with the main panel 

16 

Learn Dets.  

Any gas detectors connected to the system will require “learning”. First ensure all detectors are set to a 
unique ID address using the selector switch on the detectors themselves (address’s 1 to 4). Having 
addressed each detector, press the learn Dets button (

13

), the system will scan and store any connected 

detectors.  
 

Shows Dets 1&2, 3&4. 

 

To verify that all detectors have been successfully learnt use the Show Dets buttons 14/15 to verify the 
detectors are connected correctly.

 

 

    13, 14 & 15 Learn and Display Detectors 

13 

14 

15 

Summary of Contents for AGDS-V

Page 1: ...to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commis...

Page 2: ...Medem UK Ltd such that they only require to be connected to the panel and functionally tested In the event of a high alarm from one of the sensors the system will isolate the gas supply by closing a...

Page 3: ...r detectors Methane LPG CO CO2 Oxygen Temperature 10 Panel Mode switches factory set do not alter 11 Internal tone on off 12 Spare 13 Learn field device button press once only when all detectors are c...

Page 4: ...e commissioned a er installa on by Medem UK This will extend the warranty period from 5 years to 10 years and ensure the system is working as designed Please see warranty condi ons that came with the...

Page 5: ...ctions for more guidance AGDS V Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one another daisy chain Address...

Page 6: ...d between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional informati...

Page 7: ...d be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicato...

Page 8: ...er Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry...

Page 9: ...lay that all the detectors have been recognised by the panel 10 At this point press the reset button the panel will open the gas valve Checklist AGDS V Please do not hesitate to call for advice on the...