Medem (UK) Limited
L&M Business Park , Norman Road
Altrincham, Cheshire,
WA14 4ES
Tel: +44 (0) 161 233 0600
Fax:+44 (0) 161 233 0601
Website: www.medem.co.uk
e-mail:[email protected]
Cert No. 10213
AGDS-MC
Connections to panel: marked on board
1.
Live & Neutral 230 volts supply from 3amp switched fuse spur
2.
230 volts out to gas solenoid valve (5amp relay)
3.
Earth connection terminals
4.
Gas On BMS relay (potential free contact, mains rated, max load 5amp)
5.
Remote emergency stop buttons SELV, multiple buttons connect in series (requires a N/C circuit, open for alarm)
6.
Power connections for detectors, Methane, LPG, CO.
7.
Comms connections for detectors, Methane, LPG, CO.
8. Unused
Option
button.
9.
Display detectors addressed 9 to 16.
10. Display
detectors addressed 1 to 8.
11. Option
Switches
12.
Learn Detectors - Press after connecting & addressing Medem gas sensors.
13.
Enable/Disable Internal toner
14.
Optional Dual BMS relay (SELV) - Factory fit only, must be requested at point of order
Option Switches (No 11) Relay A
Relay B
Opt A - Off
Factory set
Factory set
Opt A - On
Factory set
Factory set
Opt B - Off
Low gas alert
High gas alert
Opt B - On
low & High gas alert
Emergency Stop