Technical data sheet  

 

The model AGD-MC consists of a mains powered panel capable of operating up to four combustible gas detectors and 
four Carbon Monoxide detectors. 
Up to sixteen detectors (combustible or CO) can be connected to the AGDS-MC when used with the external transformer 
pack. See separate schematic for wiring the transformer pack, designed for when more than four combustibles are to be 
used. 
 
The detectors are connected by low voltage 4 wire cable (typically telephone cable) daisy chained back to the control 
panel. The sensor units may be mounted up to 100mtrs from the control unit. The complete system is designed to comply 
with the latest CE Directives including the low voltage directive. 
 
This is housed in an IP65 rated ABS enclosure measuring 183mm high x 212mm wide x 97mm deep. 
This is also the power pack box size AD-PP.

 

 

The LED indications on the panel: 

Power on   

Green 

Gas on 

 

Red 

Alert   

 

Yellow 

 

The LCD indications on the panel: 

In the event of an alarm situation the LCD screen will display the condition that is causing the alarm and will generally 
offer a solution. The LCD display will indicate for the following, emergency shut off button activated, gas leak detected 
and which type of gas (with detector number).

 

 

Audible indications: 

An internal buzzer is provided to give the following sounds: 
Alarm, beep every 1 second. 
There is an option to disable the alarm buzzer on the panel circuit board by removing a jumper plug. 
 

Relay outputs: 

Main valve relay rated at 5 amps to provide a switched live to the main solenoid valve. 
230 volt rated potential free changeover alarm relay to activate a remote sounder and or beacon or signal a 
BMS system. 
 

Gas detection settings 

The combustible gas detectors are pre calibrated at works to detect gas at 5% of the low explosion level  
(pre alarm) and at 10% of the low explosion level (high alarm). 
The CO detectors are calibrated at 80ppm for pre alarm and 100ppm for full alarm 

AGDS-MC 

Summary of Contents for AGDS-MC

Page 1: ...The Home of Control Automation in Ireland AGDS MC Multi Channel Gas Detection System...

Page 2: ...GDS MC Gas detection system has been designed for use in boiler houses and plant rooms Up to 16 low voltage sensors for the detection of natural gas LPG or carbon monoxide can be connected to the pane...

Page 3: ...Design Features Gas detection of Natural gas Carbon monoxide and Butane Propane L P G Compact easy to install compact system with long detector life Remote signalling can be connected to B M S and fi...

Page 4: ...alarm the panel isolates the gas supply by closing the control valve At the same time a BMS and a beacon or sounder can be activated The AGDS MC normally uses 240 volt normally closed valves but it is...

Page 5: ...2mm wide x 97mm deep This is also the power pack box size AD PP The LED indications on the panel Power on Green Gas on Red Alert Yellow The LCD indications on the panel In the event of an alarm situat...

Page 6: ...ELV multiple buttons connect in series requires a N C circuit open for alarm 6 Power connections for detectors Methane LPG CO 7 Comms connections for detectors Methane LPG CO 8 Unused Option button 9...

Page 7: ...d daisy chain AD Med Sensors Transformer pack box wall mounting BOARD WIRING FOR THE AGDS MC Gas Detection Panel Mains Supply Fuse at 3 Amps Minimum 2 Sensors Maximum 4 to be connected to main panel D...

Page 8: ...D are being correctly identified With the gas available for use apply a small amount of the target gas to each detector The AGDS MC will indicate a low level alarm at 5 LEL for combustible gases 80ppm...

Page 9: ...be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commission this safety sys tem whereupon a commissioning report will be forwar...

Page 10: ...diagnostics Low Voltage Gas Detectors The maximum cable 4 core length between a sensor and the control panel should not exceed 100 metres If the distance between the main panel and the detectors is gr...

Page 11: ...for alarm 6 Power connections for detectors Methane LPG CO 7 Comms connections for detectors Methane LPG CO 8 Unused Option button 9 Display detectors addressed 9 to 16 10 Display detectors addressed...

Page 12: ...spur 230v EM Stop Buttons TT 70c Fire Alarm Series connected Addressable Gas detectors Connect in parallel Mains Rated Potential free contact Max load 5amp s latching relay Gas Solenoid 230v Example M...

Page 13: ...ioxide detectors should be installed so they monitor the general level of CO2 within the cooking area They should be mounted above standing head height and between 1m and 3m from the cooking line Care...

Page 14: ...nections in the panel TB2 TB1 TB3 Use terminals TB2 A and TB2 C TB2 TB1 TB3 Use terminals TB2 A and TB2 C Multiple Switches Wire in series Remote stop buttons can be connected to the panel terminal ma...

Page 15: ...Limited Otter House Naas Road Clondalkin Dublin 22 Tel 00353 1 461 4300 E sales modernplant ie W www modernplant ie Please do not hesitate to call for advice on the following number 00353 1 461 4300...

Page 16: ...safety product range Both companies work closely to ensure the products remain best in class We stock a comprehensive range of Haws AG emergency equipment We also supply special models to the highest...

Reviews: