Inputs/outputs modules: MPNE
Mect Srl
31
ME7087_13 04/21
3 = TCJ (J type thermocouple)
4 = TCK (K type thermocouple)
5 = TCT (T type thermocouple)
6 = PT100E (1 digit Resolution)
range: -40 +800°C
7 = PT100R (0.1 digit Resolution)
range: -40 +200°C
8 = TCS (S type thermocouple)
9 = TCB (B type thermocouple)
10 = TCR (R type thermocouple)
MPNE_AnIn4Conf
UINT
0
87
[RW]
Analog
input
2
configuration,
expansion 2
:
0 = not configured
1 = current
2 = voltage
3 = TCJ (J type thermocouple)
4 = TCK (K type thermocouple)
5 = TCT (T type thermocouple)
6 = PT100E (1 digit Resolution)
range: -40 +800°C
7 = PT100R (0.1 digit Resolution)
range: -40 +200°C
8 = TCS (S type thermocouple)
9 = TCB (B type thermocouple)
10 = TCR (R type thermocouple)
MPNE_AnOut1Conf
UINT
0
88
[RW]
Analog output 1 configuration -
expansion 1
:
0 = not configured
1 = current
2 = voltage
MPNE_AnOut2Conf
UINT
0
89
[RW]
Analog output 1 configuration -
expansion 2
:
0 = not configured
1 = current
2 = voltage
MPNE_AnOut1
UINT
0
90
[RW]
Analog output value - expansion 1
MPNE_AnOut2
UINT
0
91
[RW]
Analog output value - expansion 2
MPNE_AnIn1Filter
UINT
0
92
[RW]
Analog input 1 filter – expansion 1
MPNE_AnIn2Filter
UINT
0
93
[RW]
Analog input 2 filter – expansion 1
MPNE_AnIn3Filter
UINT
0
94
[RW]
Analog input 1 filter – expansion 2
MPNE_AnIn4Filter
UINT
0
95
[RW]
Analog input 2 filter – expansion 2
MPNE_ExpDigitalOut
Config17_24
UINT
0
110
[RW]
Configuring digital outputs module 06
(two bits per channel)
00: Standard output (default)
01: monostable
10: PWM with duty cycle at 50% (only
for outputs 22, 23 and 24)
11: PWM with duty cycle from 0% to
100% (only for outputs 22, 23 and 24)
MPNE_ExpPulseWidth1
_ms
UINT
0
111
[RW]
Pulse duration (ms) for outputs
configured as monostable
MPNE_Frequency_PWM1
UINT
0
112
[RW]
PWM output rate for channels defined
as PWM
MPNE_PWM_OUT22_
OUT21_DC
UINT
0
113
[RW]
Duty Cycle for configured channels
such as PWM
Bit 0..7 not used
Bit 8..15 –HEX Duty Cycle – output