DER2 digital regulator instruction manual - rev. 02 - pag. 6 

 

 

3.  Inputs and Outputs: technical specifications

 

TABLE 1 : CONNECTOR CN1 

 

Terminal

(1) 

Name 

Function  

Specification 

Notes 

Exc-

 

Excitation   

Continuous Rating: 5Adc 
Transitory Rating:12Adc at peak 

 

Aux/Exc+

 

Aux/Exc+

 

Power  

40÷270 Vac, Frequency: 12÷72Hz 

(2)

 

(1)

 

UFG 

Sensing  
Range 2  

 

Range 2: 150÷300 Vac  
Burden: <1VA

 

U channel 

UFG 

UHG

 

Sensing  
Range 1   

 

Range 1: 75÷150 Vac  
Burden: <1VA

 

UHG

 

UHB

 

Jumper   
Range1  

 

 

Short for sensing   
75÷150 Vac

 

UFB

 

10 

UFB 

 

Board reference  

11 

UFB 

 

12 

UFB 

 

13 

 

Not present

 

 

14 

VFG

 

Sensing    

Range 1: 75÷150 Vac  
Burden: <1VA

 

V channel, to be 
connected in parallel to  
U channel in case of  
single phase sensing

 

15 

VHG

 

Sensing  
Range 1  

 

16 

VHB 

Scala 2: 150÷300 Vac  
Burden: <1VA

 

17 

VFB

 

Range 2   

18 

 

Not present

 

 

19 

WFG

 

Sensing    

Range 1: 75÷150 Vac  
Burden: <1VA

 

W channel, unused   
(with shorted inputs)   
in case of single phase 
sensing

 

20 

WHG

 

Sensing  
Range 1  

 

21 

WHB 

Range 2: 150÷300 Vac  
Burden: <1VA

 

22 

WFB

 

Range 2   

Star point (12 YY or 6 Y leads  

generators) is hard connected   

to AVR power supply input 

(1)

 

TABLE 2 : CONNECTOR CN3 

 

Terminal

 

Name 

Funcion  

Specifications 

Notes 

23 

Common

 

 
Active  
protections output

 

Type: Non-insulated open collector

 

Current: 100mA  
Voltage: 30V 
Max length: 30m 

(3)

 

Programmable : active 
level, activating alarm and 
delay time 

24 

A.P.O.

 

25 

Common

 

Jumper 50/60Hz

 

Type: Not insulated  
Max length: 3m

 

Selection of underspeed  
protection threshold 

(4)

 

26 

50/60Hz

 

27 

0EXT

 

Jumper for remote voltage   
control  0÷2,5Vdc 

 

Type: Not insulated  
Max length: 3m

 

Short for 0÷2,5Vdc input    
or potentiometer  

28 

JP1

 

29 

Input for remote voltage   

Type: Not insulated  
Max length: 30m 

(3)

 

Regulation: ±10 % 

(5)

 

Input for remote voltage 

control 0÷2,5Vdc or Pext

 

 

30 

PEXT

 

Input: 0÷2,5Vdc o Potentiometer 100K

 

Burden: 0÷1mA (sink) 

31 

JP2

 

Pext Jumper

 

Type: Not insulated  
Max length: 3m

 

Short for 0÷2,5Vdc input  

  

or potentiometer  

32 

±10V

 

control  ±10 Vdc   

Input: ±10Vdc

 

Burden: ±1mA (source/sink)

 

0EXT

 

Note 1) The terminals are connected to each other on the board: 2 with 3, 4 with 5, 6 with 7, 9 with 10, 11 and 12. 
Note 2) Minimum power voltage 40 Vac at 15 Hz, 100 V at 50 Hz, 115 V at 60 Hz 
Note 3) With external EMI filter 182/K (3m without EMI filter) 
Note 4) 50·(100%-

α

Hz%) or 60·(100%-

α

Hz%) where 

α

Hz% is the position relative to the Hz trimmer or the percen    

 

   tage value of parameter P[21] 

Note 5) Value not to be exceeded. The effective range depends on parameter P[16] 
 

Summary of Contents for DER2

Page 1: ...Technical Guide DER2 Digital Regulator Guida Tecnica Regolatore Digitale DER2 The world s largest independent producer of synchronous alternators 1 5 000kVA...

Page 2: ...DER2 digital regulator instruction manual rev 02 pag 2...

Page 3: ...gistry list pag 18 2 Word of configuration Parameter P 10 pag 18 3 RAM location reference activation of saturation in analog remote control pag 19 4 Volatile memory addresses pag 20 5 Fourth Status Wo...

Page 4: ...re stored in a non volatile integrated memory EEPROM The first time the regulator is turned on a default configuration will be present which satisfies the most widely requested characteristics and is...

Page 5: ...within 3 of the value set in less than 300 msec Programmable Soft start Parameters VOLT STAB AMP and Hz settable by trimmers default 50 60Hz settable by a jumper default all parameters programmable vi...

Page 6: ...al Name Funcion Specifications Notes 23 Common Active protections output Type Non insulated open collector Current 100mA Voltage 30V Max length 30m 3 Programmable active level activating alarm and del...

Page 7: ...Response The High Dynamic Response module by a inversion of the excitation voltage allows a faster reduction of excitation current than conventional regulators and consequently a smaller transient ov...

Page 8: ...tal regulator perform a visual inspection to ensure that no damage has been sustained during transportation and movement of the equipment In the event of damage advise the shipper the insurance compan...

Page 9: ...2000 Single phase on half phase F SCC0305 00 2 channels in series Parallel star 190 200 208 220 230 240 250 from 130 to 250 Single phase H SCC0303 00 Three phase H SCC0301 00 380 400 415 440 460 480 5...

Page 10: ...ced 1 Menu 4 The parameter present in parameter P 5 if three phase sensing or p 6 if single phase sensing has to be calibrated Calibration should be adjust in order to obtain 225V from the generator o...

Page 11: ...DER2 digital regulator instruction manual rev 02 pag 11 SCC0301 01 Three phase sensing 75V 150V...

Page 12: ...DER2 digital regulator instruction manual rev 02 pag 12 SCC0302 01 Three phase sensing 150V 300V...

Page 13: ...DER2 digital regulator instruction manual rev 02 pag 13 SCC0303 01 Single phase sensing 75V 150V...

Page 14: ...DER2 digital regulator instruction manual rev 02 pag 14 SCC0304 01 Single phase sensing 150V 300V...

Page 15: ...DER2 digital regulator instruction manual rev 02 pag 15 SCC0305 01 Single phase sensing 300V 600V...

Page 16: ...DER2 digital regulator instruction manual rev 02 pag 16 SCC0306 01 Single phase sensing 300V 600V generator in threephase ZIG ZAG connection...

Page 17: ...f with the default value P 16 4608 there is an excursion of approximately 7 8 Remote control of voltage The Pext input terminal 30 and 10V terminal 32 allow to obtain remote control of the output volt...

Page 18: ...rotection intervention threshold 10 USB Communications The COM connector is RESERVED for connection to supervision unit through the dedicated USB cable see fig 7 For the communication the regulator im...

Page 19: ...32767 0 0 Value used if the VOLT trimmer is disabled 20 Stability 0 32767 16384 16384 Value used if the STAB trimmer is disabled 21 Freq threshold 10 freqnom 0 32767 26214 26214 Value used if the Hz...

Page 20: ...value memorised remains set on the start up the location L 49 is initialised with the value of parameter P 15 and is kept aligned to that value Editing of location L 49 has no effect in this working c...

Page 21: ...ommands Do not use 41 Pext Vext Inputs 0 32767 Read only Analogical input or external potentiometer value 42 Setpoint 0 32767 Read only Setpoint value 43 Setpoint 0 32767 Read only Value modified by r...

Page 22: ...19 22 between 150 300 Vac scale F There are two ways to set from minimum to maximum value 1 With the VOLT trimmer which must be enabled by the Settings potentiometers menu of DxR Termi nal software 2...

Page 23: ...I respectively depend on the position of the STAB trimmer if enabled or the value of parameter P 20 if the trimmer is disabled The value of the proportional gain KP also depends on the value of the P...

Page 24: ...2 KI P 13 L 54 P 20 fig 9c drawing of the numeric elaborations of proportional and integral gain by all DER2 with STAB trimmer disabled In both cases the effective integral gain KI is obtained by mult...

Page 25: ...n d ECO46 1 5S 4 2 4 1650 9 5 30077 27607 9 5 30077 27607 ECO46 2S 4 2 4 1800 11 32704 32640 9 5 30077 27607 ECO46 1L 4 2 4 2100 9 5 30077 27607 n d n d n d ECO46 1 5L 4 2 4 2300 11 32704 32640 9 2809...

Page 26: ...ture but it also has an active function in reducing the cause In fact an adjustment ring takes control of the voltage generated when the threshold set is exceeded This reduces the voltage to the point...

Page 27: ...inutes after overload application 4 if the AMP trimmer is enabled turn it anti clockwise until the value read at location 55 becomes equal to the value read at point 3 location 45 the operation is sim...

Page 28: ...8 57 5 Hz depending on whether 50 60 is activated or not Values between 0 and 26214 correspond to an intervention that varies from 40 48 Hz to 48 57 5Hz Values between 26214 and 32767 correspond to an...

Page 29: ...allel mode provided that the regulator stay fully operational for instance with sufficient residual voltage direct supply from the phase or from PMG WARNING In case of parallel operation of the genera...

Page 30: ...oss of excitation APO TABLE 13 ALARM FLAGS AT LOCATION L 38 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 A12 A11 A10 A9 A8 A7 A6 A...

Page 31: ...t set on zero the blockage is disabled The STOP condition causes a fall in excitation with consequent switching off and successive restarting of the regulator and therefore repetition of the cycle 5 E...

Page 32: ...e to set at location 17 use the following procedure a In relation to table 15 Add up the decimal numbers corresponding to the alarms for which you want APO to be activated obtaining number B Example i...

Page 33: ...ower source to be isolated from the electrical grid for instance by a transformer The use of these types of connection is reserved to qualified personnel able to assess the operational risks of high v...

Page 34: ...rst Edition rev 01 09 16 SCC update with PD500 and PD I rev 02 03 18 Errors correction TECHNICAL REFERENCE GUIDES Titolo Link Digital Regulators MODBUS communication protocol http www meccalte com sen...

Page 35: ...DER2 digital regulator instruction manual rev 02 pag 35...

Page 36: ...34 0 96 6700103 E info meccalte es aftersales meccalte es Germany Mecc Alte Generatoren GmbH Ensener Weg 21 D 51149 K ln T 49 0 2203 503810 F 49 0 2203 503796 E info meccalte de aftersales meccalte d...

Reviews: