DER2 digital regulator instruction manual - rev. 02 - pag. 21 

 

 

NOTE (1): depending on the sensing and nominal frequency 

NOTE (2): software configuration, with jumper 50/60 disabled 

TABLE 10 :STANDARD VALUES OF THE FOURTH STATUS WORD (LOCATION L[39]) 

 

 
Sensing 

50Hz 

60Hz 

Single phase 

7988 

24372 

Three phase 

8048 

24432 

Rated frequency:  

Bit 

Function 

Value 

Default  

B0 

Not used 

B1 

Bit activating a periodical variation of reference voltage

 

B2 

Bit activating automatic compensation of the offset in voltage acquisition channels

 

4  0/1 

(1)

 

B3 

Not used 

B4 

Bit enabling reading of 50/60 Hz jumper hardware 

16 

B5 

Inversion APO 

32 

B6 

Three phase sensing active 

64 

B7 

Voltage remote control by RAM location L[49] or input saturation ( in case of overflow ) 

128 

B8 

Bit enabling reading of reference voltage by VOLT Trimmer 

256 

B9 

Bit enabling reading of stability parameter by STAB Trimmer

 

512 

B10  Bit enabling reading of underspeed protection threshold by Hz Trimmer

 

1024 

B11  Bit enabling reading of excitation current threshold by AMP Trimmer 

2048 

B12  Bit enabling reading of external voltage input

 

4096 

B13  Bit enabling DAC 

8192 

B14  60Hz active setting (jumper 60Hz closed and/or 60Hz active setting on configuration menu)

(2)

 

16384  0/1 

(1)

 

B15  Reserved 

32768 

TABLE 11 : BIT FUNCTION OF THE FOURTH STATUS WORD L[39] ( ACTIVE CONFIGURATION ) 

 

4. Volatile memory addresses 

Add. 

Add name 

Range 

Access 

Description 

32  VOLT Trimmer 

0..32767  Read only 

VOLT Trimmer Position 

33  STAB Trimmer 

0..32767  Read only 

STAB Trimmer Position 

34  Hz Trimmer 

0..32767  Read only 

Hz Trimmer Position 

35  AMP Trimmer 

0..32767  Read only 

AMP Trimmer Position 

36  First status word  

0..3200 

Read only 

Regulated voltage [tenths of volts] 

37  Second status word 

0..900 

Read only 

Frequency [tenths of Hz] 

38  Third status word

 

16bit 

Read only 

Active alarms                   

39  Fourth status word 

16bit 

Read only 

Active configuration                   

40  Commands 

16bit 

Write 

Reserved Word Commands – Do not use

 

41  Pext/Vext Inputs 

0..32767  Read only 

Analogical input or external potentiometer value 

42  Setpoint 

0..32767

 

Read only 

Setpoint value 

43  Setpoint 

0..32767  Read only 

Value modified by regulator in case of alarms, soft-start, etc.  

44  Measured Voltage 

0..32767  Read only 

Internal variable 

45  Estimated temperture 

0..32767  Read only 

Estimates temperature of exciter windings 

…  … 

 

 

… 

49 

Reference corresponding to Vext 

0..32767  Write 

Used if Vext input is disabled and voltage remote 
control by RAM location is enabled  (P[10]-Bit B7=1) 

50  Peak to peak voltage   

0..32767  Read only 

Internal variable 

51 

Three phase switch threeshold 

0..32767  Read only 

Internal variable 

52  Offset voltage  

0..32767  Read only 

Internal variable (active only in single phase sensing) 

56  Underexcitation observer 

0..32767  Read only 

Observer of underexcitation or loss of excitation 

TABLE 9 : VOLATILE MEMORY ADDRESSES

 

 

55  AMP protection threshold 

0..32767  Read only 

Intervention threshold of overexcitation protection

(1) 

54  Ki/2

P[12] 

 

0..32767  Read only 

Integral gain not considering factor 2

P[12] (1)

 

53  Kp/2

P[11] 

 

0..32767  Read only 

Proportional gain not considering factor 2

P[11] (1)

 

5. Fourth Status Word (Location L[39]) 

 

Location L[39] indicates (almost in real time) the active configuration at any given time; it is not a simple 

replication of the value recorded in parameter P[10], however, inasmuch as the bits B2, B6 and B14 adjust 

their value only on the basis of the configuration set, but also of the effective operational status of the 

DER2 at that time; for example, if the regulator is connected with three phase sensing, even if bit B6 of the 

configuration word is set on 0 (automatic recognition of single phase – three phase activation), bit B6 of 

location L[39] will have a value of 1; similarly, if the 60 Hz jumper is engaged and reading is enabled 8Bit 

B4 of parameter P[10] set on 1), bit B14 of location L[39] will have a value of 1 even if the corresponding 

bit B14 of the configuration word is set on 0. 

The values of the fourth word of status (location L[39]) are shown in table 10, on the basis of the type of 

the regulation and nominal frequency. 

Summary of Contents for DER2

Page 1: ...Technical Guide DER2 Digital Regulator Guida Tecnica Regolatore Digitale DER2 The world s largest independent producer of synchronous alternators 1 5 000kVA...

Page 2: ...DER2 digital regulator instruction manual rev 02 pag 2...

Page 3: ...gistry list pag 18 2 Word of configuration Parameter P 10 pag 18 3 RAM location reference activation of saturation in analog remote control pag 19 4 Volatile memory addresses pag 20 5 Fourth Status Wo...

Page 4: ...re stored in a non volatile integrated memory EEPROM The first time the regulator is turned on a default configuration will be present which satisfies the most widely requested characteristics and is...

Page 5: ...within 3 of the value set in less than 300 msec Programmable Soft start Parameters VOLT STAB AMP and Hz settable by trimmers default 50 60Hz settable by a jumper default all parameters programmable vi...

Page 6: ...al Name Funcion Specifications Notes 23 Common Active protections output Type Non insulated open collector Current 100mA Voltage 30V Max length 30m 3 Programmable active level activating alarm and del...

Page 7: ...Response The High Dynamic Response module by a inversion of the excitation voltage allows a faster reduction of excitation current than conventional regulators and consequently a smaller transient ov...

Page 8: ...tal regulator perform a visual inspection to ensure that no damage has been sustained during transportation and movement of the equipment In the event of damage advise the shipper the insurance compan...

Page 9: ...2000 Single phase on half phase F SCC0305 00 2 channels in series Parallel star 190 200 208 220 230 240 250 from 130 to 250 Single phase H SCC0303 00 Three phase H SCC0301 00 380 400 415 440 460 480 5...

Page 10: ...ced 1 Menu 4 The parameter present in parameter P 5 if three phase sensing or p 6 if single phase sensing has to be calibrated Calibration should be adjust in order to obtain 225V from the generator o...

Page 11: ...DER2 digital regulator instruction manual rev 02 pag 11 SCC0301 01 Three phase sensing 75V 150V...

Page 12: ...DER2 digital regulator instruction manual rev 02 pag 12 SCC0302 01 Three phase sensing 150V 300V...

Page 13: ...DER2 digital regulator instruction manual rev 02 pag 13 SCC0303 01 Single phase sensing 75V 150V...

Page 14: ...DER2 digital regulator instruction manual rev 02 pag 14 SCC0304 01 Single phase sensing 150V 300V...

Page 15: ...DER2 digital regulator instruction manual rev 02 pag 15 SCC0305 01 Single phase sensing 300V 600V...

Page 16: ...DER2 digital regulator instruction manual rev 02 pag 16 SCC0306 01 Single phase sensing 300V 600V generator in threephase ZIG ZAG connection...

Page 17: ...f with the default value P 16 4608 there is an excursion of approximately 7 8 Remote control of voltage The Pext input terminal 30 and 10V terminal 32 allow to obtain remote control of the output volt...

Page 18: ...rotection intervention threshold 10 USB Communications The COM connector is RESERVED for connection to supervision unit through the dedicated USB cable see fig 7 For the communication the regulator im...

Page 19: ...32767 0 0 Value used if the VOLT trimmer is disabled 20 Stability 0 32767 16384 16384 Value used if the STAB trimmer is disabled 21 Freq threshold 10 freqnom 0 32767 26214 26214 Value used if the Hz...

Page 20: ...value memorised remains set on the start up the location L 49 is initialised with the value of parameter P 15 and is kept aligned to that value Editing of location L 49 has no effect in this working c...

Page 21: ...ommands Do not use 41 Pext Vext Inputs 0 32767 Read only Analogical input or external potentiometer value 42 Setpoint 0 32767 Read only Setpoint value 43 Setpoint 0 32767 Read only Value modified by r...

Page 22: ...19 22 between 150 300 Vac scale F There are two ways to set from minimum to maximum value 1 With the VOLT trimmer which must be enabled by the Settings potentiometers menu of DxR Termi nal software 2...

Page 23: ...I respectively depend on the position of the STAB trimmer if enabled or the value of parameter P 20 if the trimmer is disabled The value of the proportional gain KP also depends on the value of the P...

Page 24: ...2 KI P 13 L 54 P 20 fig 9c drawing of the numeric elaborations of proportional and integral gain by all DER2 with STAB trimmer disabled In both cases the effective integral gain KI is obtained by mult...

Page 25: ...n d ECO46 1 5S 4 2 4 1650 9 5 30077 27607 9 5 30077 27607 ECO46 2S 4 2 4 1800 11 32704 32640 9 5 30077 27607 ECO46 1L 4 2 4 2100 9 5 30077 27607 n d n d n d ECO46 1 5L 4 2 4 2300 11 32704 32640 9 2809...

Page 26: ...ture but it also has an active function in reducing the cause In fact an adjustment ring takes control of the voltage generated when the threshold set is exceeded This reduces the voltage to the point...

Page 27: ...inutes after overload application 4 if the AMP trimmer is enabled turn it anti clockwise until the value read at location 55 becomes equal to the value read at point 3 location 45 the operation is sim...

Page 28: ...8 57 5 Hz depending on whether 50 60 is activated or not Values between 0 and 26214 correspond to an intervention that varies from 40 48 Hz to 48 57 5Hz Values between 26214 and 32767 correspond to an...

Page 29: ...allel mode provided that the regulator stay fully operational for instance with sufficient residual voltage direct supply from the phase or from PMG WARNING In case of parallel operation of the genera...

Page 30: ...oss of excitation APO TABLE 13 ALARM FLAGS AT LOCATION L 38 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 A12 A11 A10 A9 A8 A7 A6 A...

Page 31: ...t set on zero the blockage is disabled The STOP condition causes a fall in excitation with consequent switching off and successive restarting of the regulator and therefore repetition of the cycle 5 E...

Page 32: ...e to set at location 17 use the following procedure a In relation to table 15 Add up the decimal numbers corresponding to the alarms for which you want APO to be activated obtaining number B Example i...

Page 33: ...ower source to be isolated from the electrical grid for instance by a transformer The use of these types of connection is reserved to qualified personnel able to assess the operational risks of high v...