Electromagnetic Flowmeter M921
MEATEST
18
Operation manual
4.2
Setup menu
Setup menu provides access to flowmeter configuration and can be accessed by pressing
Enter
button from
Main menu and entering appropriate password. There are three levels of acces to flowmeter. Passwords can
be changed in
Setup menu/General/User access
. In the following tables, settings requiring Calibration access
are marked as underlined.
Access level
Default password
User
00000
Calibration
10000
Service
Only for qualified service
personal.
Table 3 : User access
4.2.1
General
Setup menu/General
Level 1
Level 2
Description
About device
Basic information about device such as serial number,
SW/HW versions and pipe diameter can be displayed
on screen.
Language
User can switch flow meter language in this menu.
Display
Backlight
Display backlight can be set on or off in this menu.
Contrast
Configuration of display contrast.
Startup screen
User can specify which screen of main menu should
be displayed after flowmeter startup.
Aux item
User can choose from various types of measured flow
to display as bottom item on Overview screen in main
menu.
Date & time
Time
Date, time and date format can be changed here. Flow
meter features backup voltage source to date and
time backup in case of power outage.
Date
Date format
User access
Change basic password
Flowmeter user acces control.
Change calibration password
Factory settings
Restore calibration points
User can restore flowmeter settings to factory
configuration here.
Restore other settings
Restore all settings
Table 4 : General settings