5.2
Ethernet Communications
Ethernet communication is available through the standard Ethernet RJ45 socket
mounted on the top of the main circuit board. Modbus TCP, BACnet/IP, SNMP,
and DNP3 Ethernet are the protocols available,
depending on the model
ordered
. Modbus TCP is always simultaneously available alongside any other
ordered protocol. Connect to an Ethernet switch or router by means of a
standard, straight Cat5 Ethernet cable. Each DTS with Ethernet connectivity has a globally unique MAC address
which is listed on the label. By default, the meter is set to a static
IP address
of
192.168.1.150
and the
default
Modbus Address, BACnet Device ID, and DNP Addresses
is
100.
The IP address can be changed to any valid IP address using the
DTS Toolbox
utility
.
Download the latest
http://www.measurlogic.com/software
. Alternatively, an e-mail can be sent to
to request the latest version of the DTS Toolbox, its Quick Start Guide, specific protocol
documentation, or MIB files for SNMP devices.
5.3
Configuring the DIP Switches
–
Communications Settings, CT Ratings and Other Options
The DTS SMX has two 8-way DIP switches that provide the user a simple and flexible interface for configuration.
The
right hand
side
block
of DIP switches (SW1) are used to set up the device’s address and baud rate for RS
-
485 interfaces, while the
left hand side
block of DIP switches (SW2) control display, digital output, and CT ratio
options.
5.3.1
Serial Communications Settings (Modbus RTU & BACnet MS/TP)
Switch 1 (Not used for Ethernet Models)
•
Baud Rate (Switch position 1)
•
Address/MAC (add switch weight when ON)
•
Switches 2-8 OFF
–
Fixed Default Address 100
•
ALL
switches ON
–
DTSConfig configurable.
•
BACnet Device ID = MAC address
Description
Switch Position Meaning and Weight
1
2
3
4
5
6
7
8
9600 Baud Rate
OFF
19200 Baud Rate for Modbus RTU
38400 for BACnet MS/TP
ON
Modbus Address or
BACnet MAC & Device ID
64
32
16
8
4
2
1
Default Address 100
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Set Address/baud with DTSConfig
ON
ON
ON
ON
ON
ON
ON
ON
EXAMPLE
OFF
ON
ON
OFF
ON
OFF
OFF
ON
9600
64
32
-
8
-
-
1
Address / MAC = 64 + 32 + 8 + 1 = 105
Baud Rate (Switch Position 1) = 9600
Ethernet Port with Link/Activity LEDs
Switch 1
Communications
Settings
Switch 2
Display/Pulse/CT Settings