3.4
5 Amp Secondary CT Daughter Board
SMX units rated for 5 Amp CT’s come with a 5 Amp connection boa
rd pre-installed as seen in the diagram below.
ATTENTION
•
Do NOT connect to the silver screws
•
Terminate on the GREEN shorting connectors ONLY
•
The silver screws must NOT be removed
Note: CTs should be connected to the same panel as the
voltage connections.
Feed WHITE Wire
through CTs on
Main Board
Terminate BLACK and
WHITE wires on
GREEN connectors.
Do NOT remove or
connect wires to
SILVER screws
Load
→
Source
A
N
B
C
Breaker
→
Make sure CT
arrows point
TOWARDS the LOAD