©Measurlogic
Page 19
MQ0051-20F
7334 S. Alton Way, Centennial CO 80112
Tel: 877-777-6567 Tel: 303-805-5252 Fax: 425-799-4780
e-mail: [email protected]
web: www.measurlogic.com
5
DTS SMX COMMUNICATIONS INTERFACE
The DTS SMX has either a Serial or Ethernet TCP/IP communications interface depending on the model ordered.
Protocols that are supported are:
•
Modbus RTU (RS-485)
•
BACnet MS/TP (RS-485)
•
LonWorks (FT-10)
•
Modbus TCP
(Ethernet)
•
BACnet/IP (Ethernet)
•
SNMP (Ethernet)
•
DNP3 (Ethernet)
5.1
RS-485 2-Wire Communications
The RS-485 port communicates using either the Modbus RTU
or
BACnet MS/TP protocol,
depending on the model ordered
.
Connection is made by means of a pluggable 3-way screw terminal
that accepts up to 2.5 mm
2
(12AWG) wire. Suggested
communications wire is 18-22 AWG twisted-pair shielded cable. To
connect multiple DTS SMX meters on the same RS-485
communications bus, the meters should be daisy-chained together.
Do not connect the meters in a STAR, RING, or other wiring topology
that is not a daisy-chained BUS
.
•
Modbus RTU Default Communications Settings:
Unless otherwise stated through correspondence or specified on the label of the DTS SMX unit, default
communications parameters for Modbus RTU over RS-485 2-wire communications are
Modbus Address: 100, Baud Rate: 9600, Parity: None, Data Bits: 8, Stop Bits: 1.
This is notated as 9600,N,8,1 100.
This factory default is denoted as all DIP switches OFF and is how each DTS SMX is shipped (See
Section
below).
•
BACnet MS/TP Default Communications Settings:
Unless otherwise stated through correspondence or specified on the label of the DTS SMX unit, default
parameters are
BACnet MAC Address & Device ID: 100, Baud Rate 38400, Parity: None, Data Bits: 8, Stop Bits: 1.
This is notated as 38400,N,8,1.
This is denoted as SW1-1 ON and SW1-2 through 8 switches OFF and is how each DTS SMX is shipped (See
Section 5.3.1
below).
Serial RS-485 2-Wire Port