16

Figure 7-1. Mounting Screw

Chassis of Customer's system

Screw M4

L=4mm max.

P.S.U. Case(thickness 1.6mm

)

 The length L of the mounting screw must be less than 4mm when measured from the case of the NMP, as shown in Figure 7-1.

Figure 7-2 NMP1K2/NMP650 de-rating curves

7.3 De-rating

7.4  Warranty

 Make sure all modules are operating within their electrical specifications, and the combined operation output power must be less than 

 the Front-End's maximum output rating: (1200W for NMP1K2; 650W for NMP650)

.

 When operated under normal conditions, the NMP has a 5-year global warranty. Please do not change components or make 

 modifications to the product, otherwise the warranty shall be void.

 When the ambient temperature is high or input AC voltage is low, the power supply needs to be de-rated according to curves shown below.

Derating Curve

Static Characteristics

L

O

A

D (

%

)

L

O

A

D (

%

)

INPUT VOLTAGE (VAC) 60Hz

90

110

130

150

264

90

100

80

70

60

50

40

 

AMBIENT TEMPERATURE (

)

20

40

50

60

80

100

-30

0

10

20

30

40

50

60

70

 (HORIZONTAL)

115VAC

230VAC

-25

230VAC ONLY

100

CONTUINUOUS

7.  Notes on Operation

7.1

 

 Front-End Mounting

Output wire gauge should be appropriately sized based on the output current of each module. The table below shows the minimum 

wire gauge required for the corresponding current. It is recommended to use red wire for +V and black wire for -V.

AWG

14

2.1

12

12

3.3

22

10

8

5.3

10

35

45

Cross Section Area

2

 (mm )

Maximum Current (A)
UL1015 (600V 105

)

7.2 Output Wiring Guidelines

Summary of Contents for NMP1K2

Page 1: ...NMP650 1K2 Instruction Manual...

Page 2: ...ns 5 1 Input Voltage 5 2 Inrush Current Limiting 6 1 Assembly Procedures 7 1 Front End Mounting 7 2 Output Wiring Guidelines 7 3 De rating 7 4 Warranty 5 3 Output Voltage Current Adjustment 5 4 Short...

Page 3: ...tive current sharing and parallel control capabilities Output voltage programmable PV Constant current level programmable PC Global or Local ON OFF control Remote sense for output module DC OK signal...

Page 4: ...ption code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Code 00 31 for NMP1K2 Code 00 01 02 03 06 07 10 16 for NMP650 NMP1K2 Code 01 00 02 03 04 05 06 07 08 09 10 11 12 13 14 15 SLOT 1 SLOT 2 SLOT...

Page 5: ...2 2 2 1 1 1 1 2 SLOT1 2 3 4 5V 36A 12V 20A 24V 10A 24V 10A SLOT1 SLOT2 SLOT3 SLOT4 V V CN81 48V 5A SLOT5 48V 5A SLOT6 5 6 2 3 4 5V 36A 12V 20A 24V 10A 48V 5A SLOT1 V V CN81 SLOT1 SLOT2 SLOT3 SLOT4 Mod...

Page 6: ...High 4 5 5 5V When the internal temperature exceeds the limit safe limit of temperature alarm Low 0 0 5V When the internal temperature is normal 3 4 GND P Ground 6 RC1 Turns the output on and off by...

Page 7: ...ANDARDS WORKING TEMP WORKING HUMIDITY STORAGE TEMP HUMIDITY TEMP COEFFICIENT VIBRATION FUNCTION 30 70 Derate at 50 refer to Derating Curve 20 90 RH non condensing RC RC Short Power ON RC RC Open Power...

Page 8: ...ower on to recover Protection type constant current limiting protection 6 1 8V 15 1 20V 6 15V 30 1 37V 15 30V 56 66V 30 55V REMOTE ON OFF CONTROL REMOTE SENSE OUTPUT VOLTAGE PROGRAMMABLE PV OUTPUT CUR...

Page 9: ...of the units Since the inrush limiting circuit mainly consists of thermistors and a relay inrush current will be much higher than the specified value if input thermistor is not allowed sufficient tim...

Page 10: ...mperature continues to increase and exceeds the safe limit value then the output will shut down automatically Please switch off the AC input remove all possible causes and then leave the unit to cool...

Page 11: ...e Remote Sense When using this function the sensing wires should either be twisted or shielded to prevent external noise interference refer to Figure 5 6 Built in remote sense circuit that is able to...

Page 12: ...LED V V V V V V V V V V V V CN81 CN81 CN81 CN81 CN81 CN81 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 CS PIN6 GND PIN1 or 2 GND GND GND GND GND GND 9 9 9 9 9 9 10 10 10 10 10 10 GND GND GND GND GN...

Page 13: ...All 6 pins must be inserted into the correct sockets Grab the circled location and lift module The power supply unit may remain hot after power off please leave the unit to cool for at least 5 minutes...

Page 14: ...e all modules are slotted into the notches circled in red securing the top cover ensure all modules are held secure by the notches and screws Please set the electric screw driver s torque setting to 6...

Page 15: ...ll decrease the voltage Once the output voltages of all modules have been tested and adjusted to the desired values the output configuration is done 10 Higher output voltage can be acquired by connect...

Page 16: ...ay be connected in parallel Before making the parallel connection adjust the voltage of each modules individually to the desired voltage and ensure the difference in voltages is less than 0 2V The com...

Page 17: ...ot 1 and slot 2 is less than 0 2V Use two 2 unit parallel copper plates accessory FAP 009 to connect the V and V terminals of slot 1 and slot 2 and use accessory and GND pins of CN81 in parallel d App...

Page 18: ...o the product otherwise the warranty shall be void When the ambient temperature is high or input AC voltage is low the power supply needs to be de rated according to curves shown below Derating Curve...

Page 19: ...HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS...

Page 20: ...le Green Blue Brown PIN NO Blank Plate Accessory BLANK NMS240 A1 3 V Series Connection Accessory A1 4 Front End Accessory Series Connection Accessory FAS 005 For 1 slot modules NMS 240 200mm NMP CN32...

Page 21: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Reviews: